Batch function timing diagram – AW Gear Meters LLC-E-BA User Manual

Page 12

Advertising
background image

AW-Lake Company 8809 Industrial Drive, Franksville, WI 53126  web: www.aw-lake.com

 Tel: 262-884-9800  Fax: 262-884-9810  Email: [email protected]

REV. 1.3 LLC-E-BA Manual rev 3.3.10.DOC

12


mA

=s (+/-) Output - Active in the RUN mode, this analog output is batch progress signal or with

software revision 1.18 or higher can alternately indicate the currently selected batch number. The mA
output is available on terminals 1&2. See the O-set mA

=s variable description for more information.

Batch Progress Signal – Signal directly corresponds with the progress of the batch where 4 mA
equals zero progress and 20mA is equal to the full batch amount.
Batch Number Signal – Value of mA indicates batch number in one mA increments with 5 – 13
representing batch numbers 1-9. To assign the output to the Batch Number Signal function it is
necessary to wire a jumper to the back of the LLC-BA controller between lower connector terminal 11
and terminal 13.








Batch Function Timing Diagram

B A T C H

D O N E

B A T C H

P R O G R E S S

D E L A Y

S L O W

S T A R T

4 m A ( t y p . )

2 0 m A

0

L O W F L O W

P R E C U T

S L O W

S T O P

S L O W

S T A R T

D E L A Y

A N A L O G

O U T P U T

B A T C H

R E S E T

R E L A Y 2

S T A R T

S T A R T /

S T O P

R E L A Y 1

S T A R T

S T O P

S T A R T

B A T C H

R E S E T

B A T C H

T O T A L

H I G H F L O W

L O W F L O W

H I G H F L O W

Advertising