Appendix a: hdt power-on sequence, timing diagram, Appendices page 19 – COSA Xentaur Xentaur HDT User Manual

Page 26

Advertising
background image

Appendices

page 19

Appendix A: HDT power-on sequence, timing diagram

Decision tree and Timing diagram of HDT current loop during power on startup

Loop Current (mA)

Time (sec)

0

4

8

1

21

62

02

42

83

2

0

4

20

10

If the HDT is in Normal Addressing Mode (this is the

factory default), then the current loop is tested for

voltage and impedance to verify sufficient capability to

have at least 5VDC across transmitter when pulling

20mA.

Normal Addressing Mode

Current corresponds to

measurement

Polling Mode (stay at 4mA)

Loop Voltage too low (stay at 3.8mA)

EEPROM Checksum Fault (stay at ~3.8mA)

4.0mA for 8 sec

4.5mA for 8 sec

~3.5mA

for 4 sec

~15mA/sec

90% of final reading

100% of final reading

If the HDT is in Polling Mode, then the loop test is

bypassed the HDT begins measuring and loop goes

to 4mA within 5 seconds of powerup. Data is obtainable

only through the HART digital interface.

Advertising