n:: Observe correct polarity when terminating all input/output field wiring. Failure to do so may

result in circuit damage on power up.

3. If applicable, connect a normally open momentary remote mounted switch to the lugless terminal strip

(labeled RESET) located on the controller mother board (see fig 2).

4. If applicable, terminate the discrete 4-20 mA output to external device(s). Terminals are labeled “(+) 4-20”

and “(–) 4-20”.

5. If applicable, terminate the RS-485 serial output to external device(s). Terminals are labeled “A (+)”, “B

(–)”, and “SHLD”. An additional set of RS-485 terminal are provided for the connection of additional
devices.

6. Refer to installation and wiring detail of remote mount sensor assemblies as detailed in section 3.0.

Terminate field wiring from sensors to Model 1610-N1 rack lugless terminal strips located on the con-
troller mother board (see fig 2).

7. Alarm relay outputs may be discrete, zoned, or common via gold plated jumper tabs. Configure accord-

ingly.

N

No

ottee:: Based on the application and use of relay contact outputs, complete all wiring terminations prior to

application of power. Shut-in controls may be omitted until system test is complete.

1.5 S

TART

-U

P

Upon completion of all field wiring apply 24VDC power to the 1610-N1 rack. Note that each Model 10B
controller digital display illuminates. Varying readings may occur during sensor warm-up. A 10 second
alarm delay will occur on power up. Refer to sections 2.0 and 3.0 for additional start-up detail.

1.6 M

AINTENANCE AND

R

EPAIR

The Detcon Model 1610-N1’s modular design allows for minimum down time during maintenance and/or
repair. A Model 10B control module may be changed by turning the latch knob clockwise until it stops
and then sliding it out of the panel by pulling on the latch knob. To install, slide the 10B control module
into the 1610-N1 control enclosure and then secure by turning the latch knob counter-clockwise until it
stops. See section 3 for more information on the 10B control module.

1.7 S

PARE

P

ARTS

0224

Gold plated jumper tab

910-000008-003Model Series 10 Blank Plate

1.8 W

ARRANTY

Detcon inc., as manufacturer, warrants under intended normal use each new Model 1610-N1 rack control
enclosure to be free from defects in material and workmanship for a period of one year. The warranty peri-
od begins from the date of shipment to the original purchaser and ends one year thereafter. All warranties
and service policies are FOB the Detcon Inc. facility located in The Woodlands, Texas.

Detcon Model 1610-N1 Rack Panel Mount Control Enclosure PG.4

Shipping Address: 3200 A-1 Research Forest Dr., The Woodlands, Texas 7381

Mailing Address: P.O. Box 8067, The Woodlands, Texas 77387-8067

phone 888-367-4286, 281-367-4100 • fax 281-292-2860 • www.detcon.com • [email protected]