Specifications – Detcon 1000 User Manual
Page 9

Mdl 1000 H2S E-Chem / Inst. Air
Model 1000 H2S E-Chem w Instrument Air
Rev. 1.1
Page 5 of 28
2. Specifications
Sensor Type
Electrochemical
cell
Measurement Range
0-10ppm
H
2
S, up to 0-10,000ppm H
2
S
Accuracy/Repeatability
±10% of reading or ±0.5ppm, whichever is greater
Response/Clearing Time
T80 < 1 minute
Operating Temperature
-40°F to +122°F: -40°C to +50°C
Outputs
Linear 4-20mA DC; RS-485 Modbus™; 3 relays (alarm 1, alarm 2, and fault), Contacts rated 5 amps
Input Voltage
110~220VAC;
10~30VDC
Power Consumption
700mA (16.8 watts)
Electrical Classification
Explosion Proof; Class I, Division 1, Groups C, D
Sensor Life/Warranty
Sensor: 6 month conditional warranty; Transmitter: 2 year warranty
Analyzer Weight
70
lbs.
Dimensions
29” X 29” X 8”