Signal Zoning Module - Part #500-503200-000

Gas Detection System Accessory

Operator's Instruction Manual

D

ESCRIPTION

Detcon Part #500-503200-000 signal zoning module is a 4-20 MA multiplexer designed to receive up to 8
inputs and continuously output the highest signal. The circuit can be used to zone sensors to a single con-
trol module, computer or other recording device, reducing installation cost while expanding detection cov-
erage. Field wiring from the controller to the zoning module consists of 4 conductors; +24 VDC, common,
+4-20 MA and signal common.

Note: All 4-20 milliamp signals (8 inputs and 1 output) must loop to the same common (-24
VDC) source.

Z

ERO AND

S

PAN

A

DJUSTMENTS

The zero and span adjust potentiometers are factory set and should require no further adjustment. If
adjustment is necessary follow the procedure below to calibrate.

Tools required: Jewelers screwdriver and a digital volt-ohm meter capable of reading milliamps DC.

01. Remove all signal inputs from the signal input connector.
02. Install a 250 ohm resistor from the 4-20 MA output terminal to the common terminal.
03. Place the digital test probes in TP1 (+) and TP2 (–).
04. Adjust the zero potentiometer (R9) until the volt-meter reads 40 millivolts (this corresponds to 4 MA).
05. Input a 20 milliamp signal into one of the 8 signal input terminals.
06. Adjust the span potentiometer R12 until the volt-meter reads 200 millivolts (this corresponds to 20 MA).

Calibration is complete.

Shipping address: 3200 A-1 Research Forest Dr., The Woodlands, Texas 77381

Mailing address: P.O. Box 8067, The Woodlands, Texas 77387-8067 ❏ Phone: (281) 367-4100 ❏ Fax: (281) 292-2860

detcon inc.

TP2

TP1

24

MA

1

2

3

4

6

7

8

5

R9 ZERO

R12 SPAN

24 VDC IN

4-20 MA OUT (Loop to Common)

DISCREET 4-20 MA INPUTS