Specifications

General Specifications

Enclosure

Folded Stainless steel

Temperature Range

-40

°

F to 180

°

F (-40

°

C to 80

°

C)

Environmental

Hermetically Sealed Contact Switch

Encapsulated in Polyurethane

NEMA Rating

1, 2, 4, 4X, 5, 12

Protection Class

IP 66

Response Time

1 msec (5.4VA); 10 msec (150VA)

Life Cycles

100,000 Under Full Load;

Up to 200,000,000 Under Dry Circuit

Lead Types/O.D.

Armored Cable (A) 3/16" Stainless

Steel with two 18 AWG wires/0.7"(0.18cm) Each

UL/CSA

All Models

PART NUMBER

CONTACT

1

LOAD RATING

SWITCHING VOLTAGE

SWITCHING CURRENT

CONTACT

NOMINAL SENSE RANGE

2

BREAK RANGE

LEAD LENGTH

CONFIG.

AC/DC

MAXIMUM, AC/DC

MAXIMUM, AC/DCRESISTANCE

Max. Min.

NOMINAL

NOMINAL

302-CT-03A

N.O.

2.5VA/2.5W

[email protected] [email protected]

[email protected]

[email protected]

0.5 Ohms

0.75"(1.9cm) 0.375"(1.0cm)

1.2"(3.0cm)

3'(0.9m)

302-CT-06A

N.O.

2.5VA/2.5W

[email protected] [email protected]

[email protected]

[email protected]

0.5 Ohms

0.75"(1.9cm) 0.375"(1.0cm)

1.2"(3.0cm)

6'(1.8m)

302-DT-03A

4

N.O./

150VA/NA

[email protected] NA

1.25A

3

@1.25A

NA

NA

0.75"(1.9cm) 0.375"(1.0cm)

1.2"(3.0cm)

3'(0.9m)

302-DT-06A

4

N.O./

150VA/NA

[email protected] NA

1.25A

3

@120V

NA

NA

0.75"(1.9cm) 0.375"(1.0cm)

1.2"(3.0cm)

6'(1.8m)

Warning— Each electrical rating is an individual maximum and cannot be exceeded!

1

Configuration with actuator away from the switch

2

Proximity of ferrous materials usually reduces sense range — typically by 50%. The shape and type of material cause a wide diversity of effects.
Testing is required to determine actual sense range for specific applications.

3

Can withstand inrush surge up to 4 amps. Voltage drop is 1.5V. Minimum Switch Current 30mA.

4

Do not exceed 10 switches in series.

Mounting Configurations

Perpendicular

Actuation

Door

Actuation

Parallel Actuation

Best

Best

Not Recommended

Pivot Actuation

Good

Three configurations are appropriate for safety interlock applications. The parallel
actuation can result in on/off/on signal if the actuator passes by the switch rather
than coming to rest in proximity to it. This is NOT a recommended configuration for
safety interlock applications.

Figure 2

File E 122942

LR89176

Accessories

PART NUMBER

TAMPER PROOF SCREWS & SCREWDRIVER

1953

#6 x 3/4"L Tampruf

Roundhead Screw

1954

#8 x 1-1/2"L Tampruf Roundhead Screw

1955

Tampruf

®

Screwdriver

1956

Tampruf

®

1/4" Drive Bit for #6 and #8 Screws

triac
output

triac
output

Advertising