Specifications – Edwards Signaling FSRRM24 Remote Relay Module User Manual
Page 3

P/N 3101058 • REV 02 • REB 25JAN13
3 / 4
[3] If powered from an external supply, the supply must be
installed in the same room as the control panel and their
24 VDC commons (−) wired together.
4. Relay outputs are not supervised and do not provide
current limiting. Connect relays only to power-limited
sources.
5. Terminal marking indicates contact position when the relay
is deenergized.
Specifications
Voltage
18.8 to 27.3 VDC
Current
Standby
Alarm
10 mA (zone relay operation)
26 mA (common relay operation)
70 mA
Circuit capacitance
0.03 μF, max.
Circuit resistance
13 Ω, max.
Ground fault impedance 0 Ω
Relay outputs
Quantity
Type
Style
Contact rating
5
Common, zone, or programmable, and dry
contact or +24V output via jumper selection
Form C
30 Vdc at 1 A (resistive load)
Wire size
12 to 18 AWG (0.75 to 2.5 sq mm)
Mounting MFC-A
cabinet
Operating environment
Temperature
Relative humidity
0 to 49 °C (32 to 120 °F)
0 to 93% noncondensing