Wiring – Edwards Signaling E-IDC1A User Manual

Page 2

Advertising
background image

2 / 4

P/N 3101191 • REV 02 • REB 25JAN13

Refer to “Specifications” for available address numbers.

4. Set slide switch P1 to appropriate setting. Refer to

“Operation.”

5. Mount the module on the electrical box using screws

provided with the electrical box.

6. Mount the wall plate on the module using #4-24 x 1/2 in.

(13 mm) self-tapping screws.

Figure 2: Module address

Insert

screwdriver

here

Figure 3: Module installation

Screw

4-24

screws

Module

Wall plate

Compatible

electrical box

Wiring

Wire in accordance with NFPA 72 and CAN/ULC-S524. Be
sure to observe the polarity of the wires as shown in the
diagram.

Figure 4: Module wiring

TB2

TB1

(+)

(+)

(+)

(+)

RETURN

IDC

Typical NO

Initiating device

Style D Class A

[1] [2] [4]

[3]

To next
device

From

previous

device

SLC out
SLC out

SLC in

SLC in

SLC

(+)

( )

( )

( )

( )

( )


[1] Maximum 25

Ω resistance per wire

[2] Maximum 12 AWG (2.5 sq. mm) wire; minimum 18 AWG (0.75 mm

2

) wire

[3] Refer to the control panel technical reference manual for wiring specifications
[4]

Maximum 10 VDC at 350 μA

5.

All wiring is power-limited and supervised

6.

This module will not support two-wire smoke detectors

Advertising