Wiring, Specifications – Edwards Signaling E-IDCWS User Manual

Page 2

Advertising
background image

2 / 2

P/N 3101194 • REV 02 • REB 28JAN13

Figure 2: Module installation

Screw

4-24

screws

Module

Wall plate

Compatible

electrical box

Wiring

Wire in accordance with NFPA 72 and CAN/ULC-S524. Be
sure to observe the polarity of the wires as shown in the
diagram.

Specifications

Communication line voltage

Maximum 20.6 V peak-to-peak

Current

Standby
Activated


550 μA

725μA

Ground fault impedance

10 kΩ

Operating environment

Temperature
Humidity


32 to 120° F (0 to 49° C)
0 to 93% RH

Storage temperature range

–4 to 140° F (–20 to 60° C)

Compatible electrical boxes

North American 4 inch square x
2-1/2 in. (64 mm) deep 2 gang box
Standard 4 in. square box 1-1/2 in.
(38 mm) deep

Wire size

12, 14, 16, or 18 AWG wire (2.5, 1.5,
1.0, or 0.75 mm

2

) (Sizes 16 and 18

AWG are preferred)

Device address

01 to 63 (64 point control panel)

01 to 126 (127 point control panel)

Initiating device circuit (IDC)

EOL resistor value
Max. circuit resistance
Max. circuit capacitance


47 kΩ, (P/N: EOL-47)

50 Ω (25 Ω per wire)

0.1 μF

Figure 3: Module wiring

Typical NO

Waterflow Switch

47

EOLR

k

47

EOLR

k

SUP.

Style B (Class B)

[1] [2] [4]

W/FLOW

Typical NO

Supervisory/

Tamper Switch

[3]

TB2

TB1

(+)

(+)

SLC

(+)

( )

( )

( )

From

previous

device

To next
device

SLC out (+)

SLC out

SLC in

SLC in (+)

( )

( )

[1]

Maximum 25 Ω resistance per wire

[2] Maximum 12 AWG (2.5 mm

2

) wire; minimum 18 AWG (0.75 mm

2

) wire

[3] Refer to the control panel technical reference manual for wiring specifications
[4]

Maximum 10 VDC at 350 μA

5.

All wiring is power-limited and supervised

6.

This module will not support two-wire smoke detectors