Edwards Signaling E-NAC User Manual

Page 3

Advertising
background image

P/N 3101195 • REV 02 • REB 28JAN13

3 / 4

Figure 3: Module wiring

From
listed

power

supply

[2] [3] [5]

[4]

24 VDC (+)

24 VDC

Circuit wired

same as

diagram above

Style Z (Class A)

[1] [2] [5] [6]

Style Z (Class A)

[1] [2] [5] [6]

Style Y (Class B)

[1] [2] [5] [6]

Style Y (Class B)

[1] [2] [5] [6]

[8]

Typical bell circuit

Typical horn or

strobe circuit [7]

47 k EOLR

Used for

Class B only

47 k EOLR

Used for

Class B only

TB2

TB1

+

+

+

+

+

+

-

-

RETURN

NAC PWR. IN

NAC

SLC

(+)

(+)

From

previous

device

To next
device

SLC out (+)

SLC out

SLC in

SLC in (+)

( )

( )

( )

( )

( )

( )

( )

Notes
[1]

Maximum 25 Ω resistance per wire. Maximum circuit capacitance of 0.1 μF

[2] Maximum 12 AWG (2.5 mm

2

) wire; minimum 18 AWG (0.75 mm

2

) wire

[3] Refer to the control panel technical reference manual for wiring specifications
[4] If the NAC power riser is used for more than one notification zone, install in accordance with the survivability from attack by fire requirements

in NFPA 72

[5] Supervised
[6] Polarity shown in alarm condition. Polarity reverses on supervisory condition
[7] Typical synchronized temporal horn/strobe circuit when configured as Class A/B auto sync signal output module through programming
[8] Transient protection (see “Transient protection caution”)