1.

Breakaway tab

Test

NFPA 72 and CAN/ULC S537 require a calibrated sensitivity
test upon completion of the original installation and following
any modifications or additions to the system. The detector can
perform this test and generate a system sensitivity report.

To test the detector:

1. Before initial testing, remove the dust cover from the

detector and notify the proper authorities that the fire
alarm system is undergoing maintenance and will be
temporarily out of service.

2. Test the detector for proper operation using a heat gun

maintaining a six-inch minimum distance. Use caution as
excess heat can damage the detector and detector
housing.

Specifications

Communication line voltage

Maximum 20 V peak-to-peak

Normal operating current

45 µA

Alarm current

45 µA

UL/ULC fixed-temp alarm rating

135°F (57°C)

Actual alarm point

130 to 140°F (54 to 60°C)

Rate-of-rise

15°F (8°C)/min.

Compatible bases

Standard: B4U, B4U-LP
Relay: RB4U
Isolator: IB4U
Audible: SB4U

Maximum spacing

50 ft. (15 m) centers

Maximum distance from ceiling
wall-mounted

12 in. (305 mm)

Storage temperature

−4 to 140°F (−20 to 60°C)

Operating environment

Temperature

Humidity


32 to 120°F (0 to 49°C)
0 to 93% RH, noncondensing at
90°F (32°C)

Certification and compliance

Manufacturer

Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL 34202,
USA

Year of
manufacture

The first two digits of the date code (located on the
product identification label) are the year of
manufacture.

North American
standards

Meets: UL 521, CAN/ULC-S530-M91,
Follow: NFPA 72, CAN/ULC-S524

Contact information

For contact information, see our Web site:
www.edwardssignaling.com.