Setting system 4/2 event activation code options – Edwards Signaling FSC Series User Manual

Page 64

Advertising
background image

Chapter 4: Dialer programming

56

FSC Series Technical Reference Manual

Setting system 4/2 event activation code

options

Table 21 lists the set of system 4/2 event activation code options and their
default values.

Review Table 21 and make changes as required. If you don’t need to make any
changes, go to “Setting IDC 4/2 event activation code options“ on page 57.

Table 21: System 4/2 event activation code options

Option Description

Values

Int Comm TR
CODE

Determines the 4/2 code that the dialer
transmits when the control panel and the
dialer are not communicating

0 to 9, and A to F

Default: AA

CS AB Test CODE Determines the 4/2 code that the dialer

transmits as the test signal when the
control panel is in an abnormal state

0 to 9, and A to F

Default: 6F

Periph Trb CODE

Determines the 4/2 code that the dialer
transmits when the control panel and one
or more remote modules are not
communicating

0 to 9, and A to F

Default: 6D

Low Batt CODE

Determines the 4/2 code that the dialer
transmits when the battery voltage is
between 19.4 and 21.4 VDC

0 to 9, and A to F

Default: 6C

Mis Batt CODE

Determines the 4/2 code that the dialer
transmits when the battery voltage is
below 19.4 VDC or the batteries are not
connected

0 to 9, and A to F

Default: 6C

AC Fail CODE

Determines the 4/2 code that the dialer
transmits when the control panel or a
remote auxiliary/booster supply has been
without AC power for longer than the
control panel’s AC fail delay setting

0 to 9, and A to F

Default: 69

Charger CODE

Determines the 4/2 code that the dialer
transmits when the battery charger circuit
can’t adequately charge the batteries

0 to 9, and A to F

Default: 6B

Gnd Flt CODE

Determines the 4/2 code that the dialer
transmits when the control panel detects
an earth ground connection

0 to 9, and A to F

Default: 66

XFMR Tr CODE

Determines the 4/2 code that the dialer
transmits when the expander transformer
in a ten-zone panel is bad or missing

0 to 9, and A to F

Default: 6A

Aux Trb CODE

Determines the 4/2 code that the dialer
transmits when the smoke/accessory
power wiring is shorted

0 to 9, and A to F

Default: 65