Specifications – Edwards Signaling E-PDD User Manual
Page 6
6 / 6
P/N 3101210 • REV 02 • ISS 28JAN13
Specifications
Communication line voltage
Maximum 20 V peak-to-peak
Operating current
Normal
Alarm
Inrush
45 µA
45 µA
1 mA
Common alarm
relay/auxiliary equipment
Unsupervised and power-limited
Quantity: 1
Type: Form C
Ratings: 2.0 A at 30 VDC (resistive)
Air velocity
100 to 4,000 ft./min
Air pressure differential
0.005 to 1.00 inches of water
Smoke sensitivity range
0.79 to 2.46%/ft. obscuration
Smoke detection method
Photoelectric (light scattering
principle)
Alarm test response time
5 seconds
Dimensions
8.70 x 5.45 x 1.90 inches
Operating environment
Temperature
Humidity
32 to 122°F (0 to 50°C)
0 to 93% RH, noncondensing
Wire size
14 to 22 AWG wire
Detector address
01 to 64 (64 point control panel)
01 to 127 (127 point control panel)
Accessories
SD-TRM
SD-TRK
SD-MAG
SD-VTK
R-LED
Remote test-reset station, magnetic
Remote test-reset station, keyed
Test magnet kit
Air velocity test kit
Remote LED alarm indicator