Smoke testing the detector, Removing the detector – Edwards Signaling ESL 500N Series User Manual

Page 3

Advertising
background image

3

ESL 500N Series

Smoke Testing the Detector

Smoke detectors should be tested in place annually using one of the
following methods:
A. Use Smoke! in a can

®

(product number SM-200), a canned

aerosol simulated smoke and follow the directions on the can.
B. Use the following steps to test the detector with smoke:

1. Hold a smoldering punk or cotton wick close to the
smoke entry openings.

2. Gently direct the smoke into the detector for 20 seconds
or until an alarm is indicated.

Be sure to extinguish the smoke source after testing! The
detector LED should stay on and an alarm should be indicated at the
control panel. Use the system reset switch to reset the detector.

Removing the Detector

To remove the detector from the mounting base, grasp the
detector and turn it counterclockwise approximately 15 degrees.
The detector should snap off of the mounting base.
To remove the detector from the mounting base when the
detector/base lock is used
, insert a small screwdriver into the
locking tab slot on the side of the base and press in while simulta-
neously turning the detector counterclockwise 15 degrees. See
Figure 7.

Figure 5. Wiring diagrams

500N Series 2-wire wiring diagram

2-wire
Initiating
Circuit

+

-

Listed Alarm Control

First
Detector

Last
Detector

EOL
Device

Model
521NCRXT
521NCSRXT

Model
521NB/521NBXT
521NCSXT

Note
The 500N Series 2-wire
detectors are polarity
sensitive.

WARNING
The system may not operate if the detector is not connected to the control unit
initiating device circuit as specified in the detector or control unit literature.

- +

- +

NC

COM

NO

Model
521NB/521NBXT
521NCSXT

CleanMe
Enabled

CleanMe
Disabled

CleanMe
Disabled

Note
CleanMe is enabled by
wiring units in reverse
polarity

500N Series 4-wire wiring diagram

Listed Alarm Control

Note
The 500N Series 4-wire
detectors are not CleanMe
compatible

500N Series 4-wire E model wiring diagram

First
Detector

Last
Detector

EOL Device

Model
541NCSXTE
541NCXTE

Model
541NB
541NBXT

Power

Listed Alarm Control

Note
The 500N Series 4-wire
detectors are not CleanMe
compatible

+

-

NO

COM

NC

NO COM

NO COM

Initiating
Cicuit

- +

- +

+ -

ESL
204-12/24V
Power
Supervision
Relay

First
Detector

Last
Detector

EOL Device

Model
541NCSRXT
541NCSRH
541NCRXT

Model
541NB
541NBXT

Power

+

-

NC

COM

NO

NO COM

NO COM

Initiating
Cicuit

- +

- +