Maintenance warning, Warning – Edwards Signaling 103I Series User Manual

Page 2

Advertising
background image

P/N 3100415 ISSUE 1

Figure 1. Installing the Jumper

1

2

3

Jumper
(Install on pins 1 and 2
for flashing)

Pin

Location

b.

For DC models: There are four 18" wire leads: black
(common), red (for activation of red LEDs), white with
green stripe or blue (for activation of green or blue LEDs-
-depending on model) and amber (for activation of amber
LEDs).

Using wire nuts, connect black lead to DC common and
connect each of the other three leads to DC hot.

5.

Turn on power and verify that the signal operates properly.

Maintenance

WARNING

To avoid the risk of injury, do not start any maintenance
when unit is energized. Reinstall lens beore energizing
unit.

The module lens exterior surfaces should be periodically cleaned
with a soft clean cloth using water and a mild detergent to main-
tain optimum light visibility. Disconnect power before cleaning.

Lens Replacement

1.

Remove (4) screws securing the lens to the base from bottom
of base and remove lens.

2.

Replace lens on base and secure with (4) screws removed in
step 1.

Steady

Flashing

1

2

3

WARNING

To prevent electrical shock, disconnect power before
removing the lens.

Cleaning

Table 1. PLC Compatibility

Operating

Max. off state

Continuous

Surge

voltage

leakage current

on current

(inrush/duration)

Cat. No.

Volts

mA

mA

A/mSeconds**

103I-RBA-G1

24V DC

5

55

0.070/8

103I-RGA-G1
103I-RBA-N5

120V AC

5

45

0.100/8

103I-RGA-N5
*All AC volts at 60 Hz

** Amps/milliseconds