Maximum signal loss allowed [1]
5532M Amplifier Circuit Maximum Wire Length Calculation
Use this worksheet to determine the maximum wire length of
an Audio Amplifier appliance circuit. Fill in one worksheet for
each Audio Amplifier appliance circuit connected to the panel.
Wire length matrix
Wire lengths in the following table are based on a voltage drop
of 1.6 volts or 15% of the Panel's audio output End of line
appliance.
Wire resistance per 1000 ft/pair x 2 [2]
(2x the number in note 2)
Total operating current required
Maximum wire length
V
x
1000
/
ohms
ohms
/
A
ft
Current
Maximum wire length (ft)
required (A)
18 AWG
16 AWG
14 AWG
12 AWG
0.25
584
950
1460
2170
0.50
292
474
730
1084
0.75
194
316
486
722
1.00
146
236
364
542
1.25
116
190
292
434
1.50
92
158
242
362
Notes
[1] 1.6V
rms
loss in order to produce 75 dBA minimum.
[2] Use 1.6 for 12 AWG and 2.5 sq mm wire, 2.6 for 14 AWG and 1.5 sq mm wire, 4.2 for 16 AWG and 1.0 sq mm wire and 6.6