Connecting a ctm module – Edwards Signaling FireShield 10 Zone User Manual

Page 21

Advertising
background image

Installation

FireShield Technical Reference Manual

2.11

Connecting a CTM module

The CTM4.7 City Tie Module is an interface between the
control panel notification appliance circuit and a master box. It
provides off-premises signal transmission for systems that
must comply with NFPA requirements for Auxiliary
Protective Systems. The CTM4.7 activates a local energy fire
alarm box, which provides a 24 Vdc alarm signal (current
limited at 200 mA). The 4.7 K

Ω

end of line resistor required

by the NAC is built in to the CTM4.7.

Requirements

When connecting a CTM to the panel, the following hardware
and programming requirements must be met:

•

The NAC used must be dedicated to CTM use only

•

All alarm zones must be programmed to activate the
dedicated NAC

•

The NAC used must not be programmed for Signal
Silence

Specifications

Power: Nominal 24 Vdc @ 200 mA
Municipal box operation: Nominal 24 Vdc
Maximum wiring resistance: 25

Ω

Trip current: 200 mA into 14.5

Ω

coil

Maximum current: 300 mA
Standby current: 20 mA
Mounting: Single gang box
Operating environment

Temperature: 32 to 120 °F (0 to 49 °C)
Humidity: 93% RH, noncondensing

The following are wiring diagrams showing how the polarity
switches during an alarm condition.

Panel in normal condition

Notification

appliance circuit

1

1

2

2

CTM4.7

+

+

+

+

_

_

_

_

[1] [2]

Master box

Municipal circuit

Normal condition

[3]

[4]

[5]

Panel in alarm condition

Notification

appliance circuit

1

1

2

2

CTM4.7

+

+

+

+

_

_

_

_

[1] [2]

Master box

Municipal circuit

Alarm condition

[3]

[4]

[5]

Notes

[1] 200 mA into a 14.5

Ω

trip coil max., loop resistance = 25

Ω

[2] This circuit is nonpower-limited and is supervised for

grounds and opens, but not shorts

[3] Supervised and power-limited

[4] NAC must be programmed for continuous signal

[5] CTM4.7 must be mounted in the same room as the panel

Advertising
This manual is related to the following products: