2. Installation

Wiring the Relay Terminal Blocks

12

ACM-8RF PN 50362:C 03/21/01

Wiring the Relay Terminal Blocks

The ACM-8RF provides eight relays with Form-C contacts rated for 5 amps.

Note: Wiring from these relays is not supervised.

The terminal assignments are illustrated below. For information on wiring
limitations, refer to "UL Power-limited Wiring Requirements" on page 17.

Figure 4 Relay Terminal Assignments

1 2

O

F

F

1

2

3

4

5

6

7

8

O

F

F

A

C

M8R

F

-re

la

y

.c

d

r

Normally Open
Common
Normally Closed

Relay 1

Relay 2

Relay 3

Relay 4

Relay 8

Relay 7

Relay 6

Note: All Relays have the same terminal
assignment position as those on relay #4 & #5

Relay 5

Normally Open

Common

Normally Closed