Configuring the APS-6RF
2. Installation
APS-6RF Instruction PN 50893:B 7/20/00
15
Configuring the APS-6RF
The APS-6RF may be configured for the following:
• 8-hour delay for reporting loss of AC: cut jumper JP2.
• 16-hour delay for reporting loss of AC: cut jumper JP2 and JP3.
• 240 VAC operation: cut jumper JP1.
The figure below illustrates the location of the jumpers:
Figure 7 Configuring the APS-6RF