2.1.7 Connecting AC Power
At installation, connect the AC terminals to the power source as shown in Figure 2.10. It may be
necessary for a professional electrician to make this connection.
Module
Voltage
Standby
Current
Alarm Current
ECC-125DA
120 VAC, 60 Hz
300 mA
2200 mA
ECC-125DAE
240 VAC, 50 Hz
250 mA
1250 mA
Figure 2.9 ECC-125DA AC Current Draw