Fire-Lite DACT-UD2 Digital Alarm Communicator/Transmitter User Manual
Page 15

DACT-UD2 Installation
DACT-UD2 Communicator PN 53037:B 4/01/08
15
7. Align the mounting holes in the DACT-UD2 module with the newly installed
standoffs on the FACP main circuit board
8. Secure the module to the standoffs on the main circuit board with two of the
screws supplied with the DACT-UD2 and the supplied male/female standoff
which becomes the new Keypad/Display support in that location (see Figure 2.4)
Note: It is important that the supplied hardware be used to secure the module in
order to help protect against electrical transients.
9. Reinstall Keypad/Display on the main circuit board by positioning the unit over
the appropriate standoffs and securing with screws which were loosened in step 3
10. Remount the main circuit board assembly to the chassis using screws and
standoffs in their original locations. Plug in the power supply cable at J1 on the
main circuit board
11. Make certain to program the control panel for DACT-UD2 operation
12. Refer to "Digital Communicator" on page 10, before proceeding with this step.
Connect the premises primary and secondary phone lines to the DACT-UD2 as
illustrated in Figure 2.5 and test the system for correct operation
Figure 2.3 DACT-UD2 J1 Connector to FACP J2 Connector
J5
J2
Standoff 3
Standoff 2
Standoff 1
J1 Connector located on back
of DACT-UD2 module
96dialx2.CDR
Figure 2.4 DACT-UD2 Installation on Standoffs
Mounting Screw
male/female standoff
96dialx3.CDR
Mounting Screw