Finally, select the ‘Register’ option. If the register operation has been successful, the
following screen appears.
Fig. 19
Where this is unsuccessful a screen similar to the above appears indicating an error.
•
Error on answer
: Received data incorrect. Try again. If the error persists
contact the technical service.
•
VA unreachable
: There is a problem in the local network. The network cable
may be disconnected or the IP address for the IPDACT or gateway is incorrectly
configured.
•
No answer
: There is a problem in the connection with the VisorALARM. This
possibly is a problem in the client’s connection to Internet, Internet or the
network on the central side.