MS-9050 Series Manual — P/N 52413:G 4/14/2014

69

Master Programming Level

Programming

types and responses. To select the type of monitor module being programmed, press the 2 key
while viewing the Edit Monitor Screen #2. This will cause the control panel to display the first
Monitor Type Screen as illustrated below

To view additional Monitor Type Screens, press the down arrow key. While viewing one of the
Monitor Type screens, select the type of monitor module being programmed by pressing the corre-
sponding keypad number key. The display will return to the Edit Monitor Screen #2 which will
show the new type selection. The following table lists all of the Monitor Types available for pro-
gramming and their respective functions.

Monitor module type selection will affect the function of the point as follows:

Monitor Type

Action When Activated

Pull-Station

Fire Alarm

User-Defined-1

Fire Alarm

Waterflow

Fire Alarm Delayed (uses waterflow delay)

User-Defined-2

Fire Alarm Delayed (uses waterflow delay)

Monitor

Fire Alarm

User-Defined-3

Fire Alarm

Future Use

Future Use

Future Use

Future Use

Smoke-Conventional

1, 2

Fire Alarm

User-Defined-5

2

Fire Alarm

Heat-Conventional

2

Fire Alarm

User-Defined-6

2

Fire Alarm

Medic-Alert

3

Piezo, latching

User-Defined-7

Piezo, latching

Hazard-Alert

3

Piezo, latching

User-Defined-8

Piezo, latching

Tornado-Alert

3

Piezo, latching

User-Defined-9

Piezo, latching

Future Use

Future Use

Future Use

Future Use

Tamper

Supervisory, nonlatching (tracking)

User-Defined-11

Supervisory, nonlatching (tracking)

Supervisory

Supervisory, latching

User-Defined-12

Supervisory, latching

Supervisory-AR

4

Supervisory, nonlatching (tracking)

User-Defined-13

Supervisory, nonlatching (tracking)

HVAC OVRRIDE

5

Switch Supervisory, nonlatching (tracking)

Power-Monitor

AC Fault

User-Defined-14

AC Fault

Trouble-Monitor

Trouble

User-Defined-15

Trouble

Proc-Mon

3

Piezo

User-Defined-16

Piezo

Procmon-AR

3, 4

Piezo, nonlatching (tracking)

User-Defined-17

Piezo, nonlatching (tracking)

Future Use

Future Use

Future Use

Future Use

Ack-Switch

Acts like panel Acknowledge Key

Sil-Switch

Acts like panel Alarm Silence Key

Reset-Switch

Acts like panel Reset Key

Table 3.1 Monitor Types

MONITOR TYPE

1=PULL-STATION

2=USER-DEFINED-1

3=WATERFLOW

Monitor Type Screen #1