Zones available – Fire-Lite MS-9600LSC Addressable Fire Alarm Control Panel User Manual

Page 148

Advertising
background image

148

MS-9600LS Series Manual — P/N 52646:B2 2/12/2010

Programming

Maintenance Programming Level

Zone types can be changed by pressing the keypad number key corresponding to the zone in each
Zones Installed Screen. Available zone types will be displayed in the resultant screens. For exam-
ple, to change the zone type for zone Z02 in the screen illustrated above, press 3. The following
screens will be displayed:

To change the zone type for Z02 to Pull Station, scroll the display until Zone Type Program Screen
#2 is displayed. Press 2 to program zone Z02 as a Pull Station zone. The display will return to the
Zones Installed Screen showing zone Z02 and the Pull Station program type. Repeat the procedure
for each zone to be changed.

IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will assign a Water-
flow silenceable zone type to the selected zone. Any signaling devices programmed to the same
zone can be silenced by pressing the Alarm Silence key or by using the auto-silence feature.

To program a waterflow circuit as nonsilenceable, refer to “System Setup” on page 100.

Zones Available

Pressing 2 while viewing Zone Setup Screen #3 will display the following screen:

The display will show all of the zones that are still available for programming. Note that an up
and/or down arrow may appear in the upper right corner of the display, indicating that additional
screens of zone information exists. Press the up or down arrow key to view additional screens.

ZONE TYPE PROG

1=MONITOR

2=SMOKE PHOTO

3=WATERFLOW

Zone Type Program Screen #1

ZONE TYPE PROG

1=MEDICAL

2=HAZARD

3=TAMPER

Zone Type Program Screen #2

ZONE TYPE PROG

1=SUPERVISORY

2=PROC. MON

3=SMOKE ION

Zone Type Program Screen #4

ZONE TYPE PROG

1=HEAT

2=PULL STATION

3=DUCT

Zone Type Program Screen #3

NOTE: Zone Types are only relevant for Central Station reporting. Changing a zone type will

only

change how it is reported to the Central Staion.

ZONE SETUP

1=ZONE TYPES

2=ZONES AVAILABLE

3=ZONE MESSAGE

Zone Setup Screen #3

ZONES AVAILABLE

01 02 03 04 05 06 07

08 09 10 11 12 13 14

15 16 17 18 19 20 21

Advertising