Slc loop setup, Setup (see – Fire-Lite PS Tools MS-9600 User Manual

Page 47

Advertising
background image

PS-Tools User Guide

636 Pt Addr. Panel

PS-Tools

04/2010

39

Figure 5-8

Configuring Primary ANN Bus

2.

In Primary ANN Bus Address, select the Module Type for each address. (see

Figure 5-8

).

3.

Click Next to configure the Detectors or click Detectors option in the left pane.

SLC Loop Setup

SLC loops provide communication to addressable detectors, monitor (initiating device), and control
(output device) modules. One SLC loop is provided by default on the fire panel main circuit board.
You can plug the optional SLC module into the connector, on the main circuit board for the second
SLC loop. The 636 Pt Addr. fire panel addressable device capacity is 159 detectors and 159
control/monitor modules per SLC loop. Since older legacy addressable devices cannot be set to
addresses above 099, you can use newer series devices for installing addresses 100 to 159. You can
mix old and new devices on the same loop.

You can configure the SLC Loop for NFPA Style 4, 6, or 7. The wiring styles Style 4 or Style 6 are
mostly used. Style 7 wiring is same as Style 6 with the added requirement that each addressable
device on the loop must have a pair of isolator modules, one on each side. To program a system for
Style 7, you must select the loop setup for Style 6. You can configure all the addressable devices to
SLC Loop 1 and Loop 2, in the SLC Loop Setup screen.