7. TECHNICAL SPECIFICATIONS

7.1. TECHNICAL

CHARACTERISTICS

Voltage measurement with LEDs
Voltage range:

12

690V AC (16400Hz), DC (±)

Rated voltages:

12/24/50/120/230/400/690V AC (16

400Hz),

DC:

Tolerance:

in compliance with EN61243-3

ELV indications:

>50VAC, >50VDC

Response time:

< 1s at 100% of any rated voltage

Working

time:

after 30s of continuous measurement, the
instrument must make a pause of 240s before
starting a new measurement.

Consumption during measurement:

approx. 50mA (battery 3V, measuring 690V AC)
(HT6, HT8)


Voltage measurement with LCD (HT8, HT9)
Accuracy indicated as [%reading + (number of digits)] at 23°C±5°C, <70%HR

AC/DC voltage

Range [V]

Resolution [V]

Precision

Input

impedance

Max voltage

10.0

690.0

0.1

(3rdg+5digits) 200K

690VAC/DC

Max input current: <3.5mA (at 690V);

Automatic AC/DC voltage detection;

Frequency range: 16 - 400Hz;

“OL”: Over Range indication

Phase detection function (HT6, HT8, HT9)
Voltage range:

100

690V

Frequency:

50 / 60Hz


Phase sequence (HT6, HT8, HT9)
Voltage range:

120

400V Phase-Earth;

Frequency range:

50/60Hz;

Measuring mode:

2 terminals on non-isolated parts


Continuity test (HT6, HT8, HT9)
Detection range:

0

500kΩ + 50%


Lamp test (HT9)
Voltage with new battery:

approx. 3kV / 240kHz

Range intensity 200-280 kHz:

approx. 100µV/m

Indications: “Test”

LED

on

Charging time before test:

<0.5 sec

Flashing frequency:

2Hz

Test time:

typically <2 sec

Working time:

may operate in continuous mode

Consumption during test: approx.

500mA