AIR FROM OTHER INDOOR SPACES

FIGURE 9E.

The confined space should be provided with two permanent

openings, one commencing within 12 inches (300 mm) of the top

and one commencing within 12 inches (300 mm) of the bottom of

the enclosure. See Figure 9E.

Each opening should communicate directly with an additional

room(s) of sufficient volume so that the combined volume of all

spaces meets the criteria for an Unconfined Space.

Each opening should have a minimum free area of 1 square inch

per 1,000 Btu/hr (1100 mm

2

per kW) of the aggregate input rating

of all appliances installed in the enclosure. Each opening should

not be less than 100 square inches (645 cm

2

).