Venting supports, Vertical installation requirements, Horizontal installtion requirements – A.O. Smith VB/VW- 1000 User Manual

Page 17

Advertising
background image

17

VENTING SUPPORTS

Care must be taken in the installation of the venting system that

adequate support is maintained throughout the installation process.

When extending more than 10 feet (3.0m) vertically, vertical support

kits are required once every 10 feet (3.0m) of vertical run. Vertical

support is also re quired immedi ately after any transi tion (elbow,

tee, etc.) to vertical of over 10 feet (3.0m) of run and after any

offset in the vertical run.

The support brackets (supplied in the Vertical Support Kit) are to be

secure ly fastened to a solid vertical member of the building using the

appropriate fasteners; i.e., wood screws for wood framing, machine or

tapping screws for structural steel or masonry anchors for solid masonry.

The bracket should be located so that it will not interfere with any joints of

the venting system. The bottom most support bracket should be located

directly above the first transition from horizontal to vertical, see Figure

10. Refer to Figures 12, 12A, 12B and 12C.

If a means of support for the brackets are not available and

horizontal vent sections are present, install hanger straps

(made from non-combustible material) as close to the points of

transition as possible. If the horizontal portions of the vent and/or

vent connector are longer than 6 feet (2.0m), then install hanger

straps every 6 feet (2.0m) to support the connector.

DO NOT rivet or screw the straps to the conduit or other wise

puncture the conduit wall. Instead, wrap an extra loop of strap

around the conduit to hold it in position, or attach the strap to

the center screw of the double wall AL 29-4C

®

vent coupling, if

applica ble.

VERTICAL INSTALLATION REQUIREMENTS

1. The vent system must terminate at least 3 feet (1.0m)

and no more than 6 feet (2.0m) above the roof line and

no closer than 10 feet (3.0m) from any wall or verti cal

structure. If the exhaust vent terminal is within 10 feet

(3.0m) of a wall or parapet, it must extend a minimum of

2 feet (610mm) above the wall or parapet, see Figures

11 and 12A.

2. For direct vent installations, the total distance of the vent system

from the boiler vent connector to the vertical vent termination shall

not exceed 70 equivalent feet (21.3m). A maximum of three 90°

elbows can be used. Minimum vertical vent is 7 equivalent feet

(2.1m) for direct vent installations. Standard minimum vertical vent

length is 7 feet (2.1m), plus Boot-Tee. See Figures 11, 12A, 12B, and

12C for differences between standard and direct vent installations.

3. An AL 29-C

®

Vent Vertical Vent Terminal must be used at

the termina tion.

4. Maintain a minimum of 6 feet (2.0m) separation between

the air intake and the exhaust terminals.

HORIzONTAL INSTALLTION REQUIREMENTS

1. The vent system must terminate with a AL 29-4C

®

Vent

Through-the-Wall Termination (TWT). Plan the terminal

location based on the dimensions shown in Figure 9. Do

not locate the terminal within 8 feet (2.5m) of an inside

corner of a building or adjacent to outside walls, shrubs or

other such objects that may cause adverse wind conditions

in the immediate area.

2. The TWT shall be located not less than 12 inches (305mm)

above grade or, in geographical areas where snow

accumu lates, no less than 12 inches (305mm) above the

antici pated snow line. Ensure that the TWT is protected

against blockage which may occur during ice build up or

snowstorms.

The TWT shall terminate at least 3 feet (1.0m) above

any forced air inlet within 10 feet (3.0m), except when

the forced air inlet is the combustion air intake of a

direct vent appliance. The TWT shall terminate at least

4 feet (1.2m) below, 4 feet (1.2m) horizontally from or

1 foot (305mm) above any door, window or gravity air

inlet into any building as provided in the current edition

of the NATION AL FUEL GAS CODE ANSI Z223.1, see

Figure 9.

In addition, a minimum clearance of 4 feet (1.2m) hori-

zontally from, and in NO CASE ABOVE OR BELOW,

unless the 4 feet (1.2m) of horizontal distance is main-

tained from electric meters, gas meters, regulators and

relief equipment.

3. This horizontal exhaust vent system must pitch upward toward

the termination at 1/4 inch per foot (21mm per meter).

4. The TWT is designed such that the building is protected

from degradation by flue gas and condensate. Howev er,

if additional protection is desired, install against the wall

a non-corrosive metal sheet under the TWT.

5. Due to the normal formation of water vapor in the combus-

tion process, horizon tal terminations must not be located

over areas of pedestrian or vehicular traffic, (i.e., public

walkways or over areas where condensate could create

a nuisance or hazard). This is especially true in colder

climates where ice buildup is likely to occur. A.O. Smith

Corporation will not be held liable for any personal injury

or property damage due to any dislodg ing of ice.

Advertising
This manual is related to the following products: