System installation, General, Hot water heating (hydronic) equipment – A.O. Smith VB/VW- 1000 User Manual

Page 22

Advertising
background image

22

SYSTEM INSTALLATION

GENERAL

If the system is to be filled with water for testing or other

purposes during cold weather and before actual operation,

care must be taken to prevent a downdraft entering the boiler

or freezing air from contacting the system. Failure to do so

may cause the water in the system to freeze with resulting

damage to the system. DAMAGE DUE TO FREEZING IS

NOT COVERED BY THE WARRANTY.

Good practice requires that all heavy piping, etc., be support ed.

Figure 13 shows a typical primary, secondary piping method.

This is the preferred piping method for most copper fin tube

boilers. Other piping methods, however, may provide good

system operation. A prime concern when designing heating

systems is the maintenance of proper flow through the unit

during boiler operation. The secondary pump should be sized

per the recommended flow rate of the boiler, see Dimension

and Capacity Data in this manual.

A system bypass should be installed, as shown in Figure

13, to prevent boiler circulation starvation when the system

zones call for reduced flow.

This bypass may also be used with multiple boilers manifolded

for reverse-return flow. This system bypass would be installed

from boiler outlet to suction side of pump.

HOT WATER HEATING (HYDRONIC) EQUIPMENT

The following is a brief description of the equipment required

for the installations noted in this manual. All installations

must comply with local code.

1. WATER SUPPLY LINE

These boilers can be used ONLY in a forced circulation

hot water heating system. Since most forced circulation

systems will be of the closed type, install the water supply

line as shown on piping diagram, see Figure 13.

Fast filling of large pipe, old radiator installations and

pressure purging of series loop systems (where high

pressures are not available) requires bypassing of the

pressure reducing valve.

Gener ally, pressure purging is not possible with a well

pump system. High point air venting is essential.

If the system is of the open type, a pressure reducing

valve will not be required as the water supply to the

system will be controlled by a manu ally operated valve.

An overhead surge tank is required. A minimum pressure

of 15 psi (100kPa) must be maintained on the boiler at

all times to ensure avoidance of potential damage to the

boiler which may not be covered by the warranty.

2. EXPANSION TANK

If the system is of the closed type, install an expansion

tank as shown in Figure 13. The sizing of the expansion

tank for a closed system is very important and is directly

related to the total water volume of the system. Refer

to “Systems and Equipment” volume of the ASHRAE

handbook.

An air separator as shown in the piping diagrams is recom-

mended especially for modern commercial hydronic systems.

3. VENT VALVES

It is recommended that automatic, loose key or screw-

driver type vent valves be installed at each convector

or radiator.

4. SYSTEM HEADERS

Split systems with individual supply and return lines from

the boiler room should normally have this piping connected

to supply and return manifold headers near the boiler. To

achieve good water distribution with maximum pressure

drop for sever al circuits, manifolds should be larger than

system mains.

The circuits should be spaced on the heater at a minimum

of 3” (76mm) center to center. Install a balancing cock in

each return line.

Manifold headers are recommended for split systems

with or without zone valves and also those installations

with zone circulators. If the system is to be split at

remote points, good practice requires special attention

be given to main pipe sizing to allow balancing of water

flow.

5. COOLING PIPING

When the boiler is used in conjunction with a refrigeration

system it must be installed so that the chilled medium is

piped in parallel with the boiler. Appropriate flow control

valves, manual or motorized, must be provided to prevent

the chilled medium from entering the boiler.

Water temperature in the heating system must be reduced

to less than 100°F (38°C) before cooling system is started,

or damage to the chiller unit may occur.

If the boiler is connected to chilled water piping or its

heating coils are exposed to refrigerated air, the boiler

piping system must be equipped with flow valves or other

automatic means to prevent gravity circulation through the

boiler during the cooling cycle.

Primary/secondary pumping of both the chiller(s) and

the boiler(s) is an excellent winter-summer change-over

method, because cooling flow rates are so much more

than heating flow rates. In this way each system (heating

or cooling) is circulated independently.

6. CIRCULATING PUMP

FOR HOT WATER HEATING BOILERS - VB MODELS, the

circulating pump is NOT provided and must be field-installed.

NOTE: If a system pump is to be installed on a VB

model, the maximum rating of the pump motor must

not exceed 1 hp.

Advertising
This manual is related to the following products: