Wiring – A.O. Smith VB/VW- 1000 User Manual

Page 28

Advertising
background image

28

WIRING

Label all wires prior to disconnection when servicing controls.

Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing. Strict adherence to the

wiring diagrams is required to prevent constant pump operation

when the system controller is satisfied. Otherwise the warranty is

void as stipulated in the limited warranty in this installation manual.
If any of the original wire, as supplied with the appliance, must be

replaced, it must be replaced with type 105°C wire or its equivalent.

Figure 16.

There are five (5) electrical connections that must be made
for the unit to operate correctly:

1. BLACK (No Stripe) 120V HOT

2. WHITE 120V NEUTRAL

3. GREEN GROUND

4. (2) TANK PROBE OR (2) ENABLE/DISABLE***

*** Enable/disable can also be used with a 24 volt thermostat.

Do not use tank probe when using thermostat.

These connections shall be made at the rear of
the unit where a junction box is provided. AN
ELECTRICAL GROUND IS REQUIRED TO REDUCE
THE RISK OF ELECTRIC SHOCK OR POSSIBLE
ELECTROCUTION. A GROUND SCREW IS PROVIDED
IN THIS JUNCTION BOX.

NOTE: Tank probes are not provided on VB models,

it is required that a system/operating temperature

controller (field supplied) be installed to regulate

loop or system temperatures. Two yellow wires are

provided in the rear junction box for this connection.

Do not operate this boiler without system or

operating control.

When operating the boiler with the tank probe the enable/disable
must be wired together.

Refer to the Connection Diagram, see Figure 17, and to

the Schematic Diagram, see Figure 18.