Inputs to mcb – A.O. Smith VB/VW- 1000 User Manual

Page 38

Advertising
background image

38

INPUTS TO MCB

TEMPERATURE SENSORS:
Temperature probes
(MCB - outlet and either inlet or tank are

required): The MCB accepts analog temperature inputs from

up to three sensors (inlet, outlet, and tank).
MRHL (Manual Reset HIGH LIMIT): The MRHL is a hi-limit switch

located inside the outlet probe. It is a normally closed switch that

opens if the probe is exposed to a temperature higher than the trip

point. Once tripped, the control system needs to be manually reset.
Thermostat input (MCB - optional): This input is set up to work with

an externally connected thermostat that provides a contact closure. If

this input is closed and everything else is in the proper state, a “call for

heat” condition will be initiated. These leads should be shorted together

when a thermostat is not being used. If it is desired that the thermostat

control the temperature of the boiler, the operating setpoint of the

system should be set higher than the temperature that the thermostat is

controlling. This will allow the thermostat to control the boiler. When the

thermostat closes, a call for heat will be generated until the thermostat

determines that the required temperature has been reached.
AIR PRESSURE SENSORS (OPEN CONDITION INDICATES FAULT):
Blocked Inlet
(MCB - required) Normally closed switch that

activates if the air inlet is blocked 3/4 or more during operation.
Blocked Flue (MCB - required): Normally closed switch that opens

if the flue becomes blocked during operation.
Blower Prover (MCB - required): Normally open switch that closes

when the air pressure produced by the blower is above the set point.
GAS PRESSURE SENSORS (OPEN CONDITION INDICATES FAULT):
Low Gas (MCB - required): Normally open switch that closes when

the gas pressure rises above the trip level. This input is enabled/

disabled by a dip switch on the MCB
Hi Gas (MCB - required): Normally closed switch that opens if the

gas pressure exceeds a set value. This input is enabled/disabled

by a dip switch on the MCB.
WATER LEVEL SENSOR (OPEN CONDITION INDICATES FAULT):
Low Water Cut Off
(MCB - optional): Normally open switch that

closes when water reaches preset level. This input is enabled/

disabled by a dip switch on the MCB.
WATER FLOW SENSOR:
Flow
(MCB - required): Normally open switch that closes when

flow exceeds a set value.

FLAME SENSOR:
Flame
(MCB - required): Returns a signal to the microprocessor

if flame is detected on the burner. If the flame rod is missing or

shorted, the flame will not be detected.
OUTPUTS FROM MCB
RELAY CONTACT OUTPUT:
Alarm
(MCB - 24VAC - optional): Provides electrical power to

operate an external alarm. This can be an audio device (i.e.,

Sonalert), a visual device (lamp), or any other device that will

operate with the voltage and current level provided.
Pump (MCB - 120VAC - required on systems that do not have

an external pump): Provides electrical power to directly operate a

pump or the coil of an externally connected contactor.
Blower (MCB - 120VAC - required): Variable speed blowers utilize

the high blower output only.
Igniter (MCB - 120VAC - required): Provides power to operate

the HSI igniters.
Gas Valve (MCB - 24VAC - required): Provides power to activate

the gas valve. The gas valve cannot be activated when the MRHL

contacts are open.
Low Water Cut Off (MCB - 24VAC - optional): Directly connected to

the 24VAC line to provide power to operate an external LWCO device.
MCB AND PDB INDICATOR LAMPS AND FUSES
A green LED is mounted on the PDB to indicate when line voltage

is applied (the PDB also contains a yellow and red LED, and a test/

run jumper that are used during installation to verify proper power

connections). A red LED on the MCB is used to indicate when the

24VAC input fuse has blown.
Yellow LEDs are located near the microcontrollers on the MCB.

These LEDs are “heartbeat indicators,” and blink approximately

twice per second to indicate that the microcontrollers are

running.
MCB JUMPERS
The MCB has two jumpers. JP1 on the MCB is used to terminate

the external communications line. It is normally left off and installed

when the external cable is very long.
IGNITERS
The EMC modulation system operates with Silicon Carbide Igniters

MCB - Ten Position Dipswitch:

Dipswitch configurations are READ ONLY ON POWER UP. These switches are only to be set at the factory or by authorized trained

personnel! Once set the boiler will operate according to the chosen options. If a switch is changed, power must be cycled before the

change will take effect. The status of all dipswitches can be observed on the system status screen on the UIM.

TABLE 13. - MCB/FCB Dipswitches:

Dipswitch Function

Switch Position

Hot Water Boilers

Hydronic Heating Boiler

Switch 1: Selection of the type of boiler application:

On = VW

Off = VB

Switch 2: Trials for ignition:

On = 3

Off = 1

Switch 3: IRI Gas Valve Not Available:

Switch 4: Controlling Probe:

On = Tank (Remote) Off = Inlet

Switch 5: Powered Venter:

On = Yes

Off = No

Switch 6: Low Water Cut Off: (LWCO)

On = Yes

Off = No

Switch 7: Low Gas Pressure

On = Yes

Off = No

Switch 8: Modulation:

On

Advertising
This manual is related to the following products: