A.O. Smith VB/VW- 1000 User Manual

Page 42

Advertising
background image

42

Use the following procedure to change the automatically resettable

High Limit Setpoint:
1. Press the MENU key.
2. Scroll the “>” with the DOWN key next to USER SETTING SCREEN.
3. Press the SELECT key.
4. Scroll the “>” with the DOWN key until it is pointing to HIGH

LIMIT SETPOINT.

5. Press the SELECT KEY.
6. Use the UP and DOWN key to select the value you wish to

enter.

7. Press the SELECT key to accept and store the new value.
• High Limit Differential:
The outlet temperature must be below the automatic High Limit

setpoint minus the High Limit Differential setpoint before a call

for heat can be generated.

HIGH LIMIT DIFFERENTIAL SETPOINT ADJUSTMENT

PROCEDURE

The High Limit Differential Setpoint has a range of 1°F to 50°F for

all models. Use the following procedure to change the High Limit

Differential Setpoint:
1. Press the MENU key.
2. Scroll the “>” with the down key next to USER SETTING

SCREEN.

3. Press the SELECT key.
4. Scroll the “>” with the DOWN key until it is pointing to HIGH

LIMIT DIFFERENTIAL SETPOINT.

5. Press the SELECT key.
6. Use the UP or DOWN key to select the value you wish to enter.
7. Press the SELECT key to accept and store the new value.
• Operating Differential Setpoints:
Each of the two stages has an independent Operating

Differential setpoint.

Temperature Units:

Temperature can be displayed in either °F or °C units.

Post Circulate Delay Time:

The time circulation pump will stay on after the burner

is turned off. The time in seconds is adjustable with the

following values: 45, 90, 180 or continuous. If the continuous

value is selected the pump will remain on at all times and

the post circulate state time will be set at 45 seconds.

Network Address:

This is a unique number assigned to this boiler to differentiate

it from other boilers or water heater on the same A. O.

Smith proprietary network. A valid Network Address can be

any number from 1 to 31. It is set by default to zero, which

is an invalid address. The boiler will not communicate until

it is changed to a valid and unique number. This prevents

two units from trying to respond to the same request from

the PC or supervisory network device.

Configuration Settings Screen:

Displays the status of the dipswitches installed on all

boards as described earlier.

Log & System Info Screen:

Displays the following information:

Elapsed hours of operation (Total time system has been powered up)
Number of running minutes (Number of minutes system has

been in the run mode)

kBtu rating of the boiler (0 to 5750kBtu in 10kBtu increments)
The software revision level of the MCB.

Current Error Screen:

Displays the last error that the system has detected plus a time

stamp of when the error occurred. (The time stamp is based

on the elapsed hours value at the time the error occurred. It

is displayed in hours and minutes. This error remain displayed

as long as it is still valid. When cleared it is moved to the Error

History Screen. The system will automatically jump to this screen

when an error is detected. It will also go to this screen upon

power-up if an error was still valid when power was turned off.

NOTE: Errors are cleared from this screen by pressing

the “select” key.

• Error History Screen:
This screen displays a list of the last 9 errors (with time

stamps) that have occurred. The last error to occur

is displayed first. If a new error occurs this screen is

presented to display the error.

• Reload Defaults Screen:
From this screen the user can restore the factory default

values for screen adjustable configurations by pressing

the Select key. The values restored are as follows:

VW Models
Oper Setpnt (Operating Setpoint) - 145° F (63° C)
Hi Limit (High Limit Setpoint) = 210° F (99° C)
Hi Limit Dif (High Limit Differential) = 20° F (11° C)
VB Models
Oper Setpnt (Operating Setpoint) = 190° F (88° C)
Hi Limit (High Limit Setpoint) = 230° F (110° C)
Hi Limit Dif (High Limit Differential) = 20° F (11° C)
Both Models
Tempert Units (Temperature Units) = F
Post Cir Secs (Post Circulation pump delay = 45 seconds
Network Address (Network Address) = (none)
UIM Touch Switches
Below the LCD display are five touch switches or keys, that the

operator uses to operate the system.
• Menu Key:
Pressing this key activates the menu screen where the other

screens can be accessed.

• Select Key:
This key performs several functions. Screens can be selected

from the menu screen by pressing this key when the “>” appears

next to the screen desired.

On the User Settings screen items that appear next to a “>”

symbol can be selected with this key. If a setpoint configuration

item is selected, the “>” will then flash slowly to indicate that

the item has been selected. The Up and Down keys are then

used to change its value.

From the Current Error Screen this key is used to reset the

system from an error: