Any safety devices including low water cutoffs used in conjunction

with this boiler should receive periodic (every six months)

inspection to assure proper operation. A low water cutoff device of

the float type should be flushed every six months. Periodic checks,

at least twice a year, should be made for water leaks.

More frequent inspections may be necessary depending on water

conditions.

The boiler-mounted gas and electrical controls have been

designed to give both dependable service and long life. However,

malfunction can occur, as with any piece of equipment. It

is therefore recommended that all components be checked

periodically by a qualified service agent for proper operation.

RELIEF VALVE

The safety relief valve should be opened at least twice a year

to check its working condition. This will aid in assuring proper

pressure relief protection. Lift the lever at the top of the valve

several times until the valve seats properly and operates freely.

COMBUSTION AIR FILTER

If the combustion air supply to the boiler contains dust, dirt, drywall

dust etc. a filter must be installed. An air filter is not supplied with

the boiler as shipped from the factory. The installer must provide a

filtering system in the air inlet to the boiler if dust, dirt or construction

dirt can be pulled into the boiler through the inlet air piping.

Periodically clean air filter per the manufacturer’s instructions.

BLOWER COMPARTMENT

The blower compartment should be cleaned annually to remove

any dirt and lint that may have accumulated in the compartment

or on the blower and motor. Buildups of dirt and lint on the blower

and motor can create excessive loads on the motor resulting in

higher that normal operating temperatures and possible shortened

service life.

BURNER MAINTENANCE

Qualified servicers should follow this procedure when the boiler’s

burner needs cleaning.

1. Turn off the electrical power to the boiler and close the main

manual gas shutoff valve(s). Allow the boiler parts to cool before

disassembly.

2. Loosen the flange and separate the gas train from the manifold

assembly.

3. Separate the burner from the blower adapter by first removing

the four (4) bolts and subsequently, the blower gas kets. The

blower should be free to move at this point.

FOR DIRECT VENT UNITS: It is necessary to loosen and slide

the rubber coupling on the blower adaptor in order to move the

blower.

4. Loosen the seven bolts on the blower adapter at the base and

move the burner ground wire (Green) aside.

5. Lift the blower adapter and remove the manifold assembly up

from the 6 studs located on the cover plate and remove the

burner gasket.

6. Remove any loose foreign material such as dust or lint with

a vacuum. Check all ports for blockage. Dislodge any foreign

material causing blockage. Remove any soot or carbon deposits

with a rag making sure to remove any lint left on the burner by

vacuuming again.

7. Reverse the steps to reassemble the unit.

8. Restore electrical power and gas supply to the boiler.

• Put the boiler back in operation by following the Lighting and

Operating instructions in this manual.

• Check for gas leaks and proper boiler and vent operation.

CONDENSATE REMOVAL SYSTEM

Due to the highly efficient operation of this unit, condensate is

formed during operation and must be removed by the conden-

sate drain systems. Inspect the condensate drains and tubes

at least once a month and insure they will allow the free flow of

condensate at all times. The system must be inspected more

frequently in cold weather if the drain system is located in an

area, such as along the floor, where freezing tempera tures are

likely to occur. The conden sate drain system must be protected

against freezing. Contact a qualified service agent to inspect

and correct the condition if freezing of the conden sate lines is a

problem. The unit is equipped with a blocked flue switch which

will shut the unit off if condensate is unable to drain and backs

up in the unit. A blocked flue error will appear when sufficient

condensate accumulates for this condition.

The transparent drain lines and condensate drain on the bottom

of the vent collector should be visually inspected at one month

intervals for blockage, particularly in the areas of the loops in the

lines which trap a small amount of conden sate, and the exit point

of the vent collector drain. Conden sate in portions of the line other

than the loop area indicates a blockage in the drain line. Flush the