Water temperature limit controls, On/off switch, Circulating pump – A.O. Smith VB/VW- 1000 User Manual

Page 9: Temperature probes, Low water cutoff (optional), Pressure relief valve, Caution, Water damage hazard

Advertising
background image

9

WATER TEMPERATURE LIMIT CONTROLS

The “V(B/W)” models incorporate an outlet water probe consisting

of two limit controls:
1. A Manual Reset High limit control that can be set as high as either

210°F (99°C) or 235°F (113°C), depending on the application.

2. A fixed manual high limit, factory set at 244°F (118°C). If

the manual reset should open due to high temperature, the

gas valves will close and unit will go into lockout. If lockout

occurs, push the SELECTION button on UIM to restart boiler.

ON/OFF SWITCH

The ON/OFF Switch is a single-pole, sin gle-throw rocker switch.

This switch pro vides 120V from the line source to the boiler.

CIRCULATING PUMP

HOT WATER SUPPLY BOILER-VW, the circu lating pump is

integral to the VW models. This pump has been lu bricated

at the factory, and future lu brication should be in accordance

with the motor manufacturer’s instructions provided as a

supplement to this manual.
HOT WATER HEATING BOILERS-VB, the cir culating pump is NOT

provided on standard models (optional) and must be obtained and

installed in the field.
NOTE: If a system pump is to be installed on a VB model,

the maximum rating of pump motor must not exceed 1 hp.

TEMPERATURE PROBES

INLET / REMOTE

TEMPERATURE

PROBE

OUTLET

TEMPERATURE

PROBE

INLET / REMOTE

TEMPERATURE

PROBE

OUTLET TEMPERATURE

PROBE

FIGURE 7. REMOTE PROBE INSTALLATION.

Temperature probes are 3/4 inch male NPT threaded immersion

probes, see Figure 7. Temperature probes have embedded

temperature sensors (thermistors). The boiler’s control system

monitors these sensors to determine water temperature at various

points in the system.
INLET AND OUTLET TEMPERATURE PROBES
All VF boilers have one Inlet and one Outlet Temperature Probe

factory installed in the top of the heat exchanger to monitor the

water temperature entering and leaving the boiler. The Inlet Probe

is a temperature sensor only and has two leads. The Outlet probe

also contains the manual reset high temperature limit switch and

has four leads. The control system displays the Inlet and Outlet

water temperatures sensed from these two probes on the default

Temperatures screen.
REMOTE TEMPERATURE PROBE
All VF boilers are supplied from the factory with a Remote

Temperature Probe. The supplied Remote Temperature Probe

is used to control system water temperature for a single boiler

in a domestic hot water storage tank or in the return line from a

primary/secondary hydronic heating system. Use of the Remote

Temperature Probe allows a boiler to sense the actual water

temperature inside the storage tank or hydronic heating loop.

The boiler will modulate its firing rate in response to the

actual system temperature and load conditions. The control

system displays the temperature sensed from the Remote

Temperature Probe as the “Tank” temperature on the default

Temperatures screen.

QUAD THERMISTOR PROBE
When connecting up to 4 boilers to a single storage tank

or one primary/secondary hydronic heating system the

optional Quad Thermistor Probe should be used. The Quad

Thermistor Probe is a remote temperature probe with four

temperature sensors embedded in one device. The Quad Thermistor

Probe allows up to 4 boilers to sense system temperature from

same point in the system. Use of the Quad Thermistor Probe

will allow each connected boiler to individually sense actual

water temperature in the storage tank or hydronic heating loop.

The temperatures sensed from each of the four temperature

sensor circuits in a Quad Thermistor Probe are shown as “Tank”

temperature on each boiler’s default Temperatures screen.

NOTE: See the Field Wiring, Remote Temperature Probe

Installation and the Primary System Control sections of this manual

for operating and installation instructions.

LOW WATER CUTOFF (OPTIONAL)

If boiler is installed above radiation level, a Low Water Cutoff Device

must be installed in boiler outlet at time of installation or, order

pre-installed from the factory. If low water detection is required by

authorities having jurisdiction, a low water cutoff switch should be

installed in the boiler outlet water line. The switch should receive

periodic (every six months) inspection to assure proper operation.

PRESSURE RELIEF VALVE

An ASME rated pressure relief valve is furnished with the boiler.

Never operate the boiler if it is not filled with water and a properly

sized pressure relief valve is not installed.
The pressure rating of the relief valve should be equal to or less

than the rated pressure capacity of any component in the system

including the boiler. Should the valve need to be replaced, call

the toll free phone number listed on the back of this manual for

further technical assistance.

Explosion Hazard

Relief Valve must comply with

ASME code.

Properly sized Relief Valve must

be installed.
Can result in overheating and

excessive tank pressure.
Can cause serious injury or death.

A discharge pipe from the relief valve should terminate at an adequate

floor drain. Do not thread, plug, or cap the end of drain line.

CAUTION

Pressure Relief Valve discharge pipe must

terminate at adequate drain.

Water Damage Hazard