4. SPECIFICATIONS

● Measurement Specification

Instrument dimensions

186Ч167Ч89mm

Instrument weight

M-4120A / 960g, M-4116A and M-4118A / 750g

Reference conditions

Specifications are based on the following conditions
except where otherwise stated:

1. Ambient temperature: 23 ± 5 ℃
2. Relative humidity:45% to 75%
3. Position: horizontal
4. AC power source: 230V, 50Hz
5. Altitude: Up to 2000m

Operating temperature 0 to +40℃, relative humidity 80% or less, no

condensation.

Storage temperature

−20 to +60℃, relative humidity 75% or less, no
condensation.

Symbols used on the

Equipment protected throughout by DOUBLE
INSULATION or REINFORCED INSULATION.

Caution(refer to accompanying instruction
manual)

and humidity

and humidity

instrument

Loop Impedance ( IEC61557-3)

Prospective Short-circuit Current (M-4118A, M-4120A)

Voltage

Range

20Ω
200Ω
2000Ω

Measuring range

0.00∼19.99Ω
0.0 ∼199.9Ω
0 ∼1999Ω

Nominal test current

at 0Ω external loop

25A / 20ms
2.3A / 40ms
15mA /280ms

Accuracy

±(2%rdg + 4dgt)

Range

200A
2000A
20kA

Measuring range

0.0 ∼199.9A
0 ∼1999A
0.00 ∼ 4.00kA

Nominal test current

at 0Ω external loop

2.3A / 40ms
25A / 20ms
25A / 20ms

Accuracy

Consider accuracy
of Loop Impedance

Measuring range

110 ∼ 260V

Accuracy

±(2%rdg + 4dgt)