5 vdc output connections – Lake Monitors Flow Transmitters User Manual

Page 35

Advertising
background image

1-5 VDC Output Connections

Wiring Instructions (Refer to Illustrations 8 and 9 above):

1) Move the programmable jumper on the signal conditioning board

into the position closest to the meter’s outlet, as shown in
Illustration 9.

2) Connect the positive voltage (+17 to +35 VDC) to terminal #1 of

the din connector.

3) Connect terminal #2 of the DIN to the 1-5 VDC input of the

receiving device.

4) If the power source does not originate at the receiving device, a

wire will need to be connected between the negative side of the
voltage source and the signal ground of the receiving device.

5) If the transmitter is operating properly, the green LED on the

circuit board will illuminate dimly at zero flow and will increase in
intensity as flow rate increases.

Page 35 / Flow Transmitters / Lake Manual

Illustration 8

Illustration 9

NO CONNECTION

ELECTRICAL CONNECTIONS - 1- 5 VDC

NO CONNECTION

249 OHMS

PIN #1

+17 - 35 VDC

PIN #2
1-5 VDC OUT

TO SIGNAL
GROUND

PROGRAMMABLE JUMPER
IN POSITION CLOSEST
TO METER OUTLET

JUMPER POSITION - 1- 5 VDC