Operation

Research, Inc.

19


REMOTE INTERLOCK The Remote Interlock alarm is a Minor
alarm. This is a customer driven feature that can be used to signal a
line stoppage or any occurrence where the heaters should be
temporarily turned off. The opening of a dry contact is required to trip
this alarm, a jumper is installed from the factory to bypass this alarm
until it is hooked up. See the schematic for the location to make the
connection.

FAST STOP The Fast Stop Alarm is a Critical alarm. It is typically
used in an emergency, where the heat needs to be turned off in a hurry.
The Fast Stop can be initiated from the operator panel (the red
mushroom switch) or it can be wired into the production line. The
opening of a dry contact is required to trip this alarm, a jumper is
installed from the factory to bypass this alarm until it is hooked up.
See the schematic for the location to make the connection.

HEATER OPEN
The Heater Open alarm is a Critical alarm. If
opened while running a very intense light would be directed at the
operator

MOTION DETECT The Motion Detect alarm is a Minor alarm. It
functions with the optional motion sensor, to set power output levels to
0 when the product is not moving. It can be enabled and disabled in
the OPTIONS menu.