Operating instructions, Controls and indicators – Precision Control Systems 930 User Manual

Page 14

Advertising
background image

Model 930 ControlIR

TM

Instruction Manual

Operating Instructions

Research, Inc.

Page 10 of 25






CONTROLS AND
INDICATORS

Main Disconnect Switch






Heater ON/OFF Switch



Cooling ON/OFF Switch

Heater On Indicator

Cooling On Indicator




Heater Over Temperature
Indicator





Lamp-Out, OCT / SCR
Indicator

Operating Instructions

Figure 4-1 shows the location of the controls and indicators.



The main disconnect switch turn on and off the power control system. Note the
following:

Before turning on the disconnect switch, check the following:
1. The load is wired and ready for power to be applied to it.

2. All safety precautions are observed.

The Heater ON/OFF switch allows the operator to enable or disable the power going to
the load. This is accomplished by removing power from the AC contactor. This in
turn removes power from the SCR controller. The cooling on indicator must be on
before the heater power can be turned on.

The Cooling ON/OFF switch allows the operator to turn on or off the heater cooling.

• Indicator light on steady indicates power is applied to the heater power controller.
• Indicator light flashing indicates that the Remote Interlock is open and heater

power can not be applied.

• Indicator light on steady indicates adequate cooling flow.
• Indicator light flashing indicates that the cooling is in a one minute shutoff delay

cycle. The one minute delay cycle is activated any time that the heater power
contactor is opened, after the initial heater on cycle is activated.


• Indicator light on steady indicates a heater over temperature condition. A heater

over temperature condition will open the heater power contactor, removing power
from the heater.

• Indicator light flashing indicates a process over temperature alarm. This feature

is available only if the Temperature Control Option is installed. The indicator
will flash only as long as the process alarm exists.


• Indicator light on steady indicates a power controller over current (OCT) or a

power controller shorted scr (SCR) condition exists. The OCT / SCR alarm will
open the heater contactor, removing power from the load.

• Indicator light flashing indicates a lamp out condition. This feature is available

only if the lamp out (LL) option is installed. The alarm will remain on as long as
the lamp out condition exists.

Advertising