Wiring Connections


The weight of the Model 915 varies slightly with the options installed. The maximum weight of
the system is 110 pounds (50 kg).

Conduit entry into the system should be made near the right side of the cabinet for power
wiring, near the center of the cabinet for load wiring, and near the left side for 120 VAC control
wiring.

Assure no metal fragments are allowed to fall into the equipment while holes are made

for conduit fittings.


We suggest a separate conduit entry should be made for low level DC control wiring if used.
This includes the remote setpoint input or thermocouple wire (temperature control option).

Wire Ratings:

Wire Temperature Rating:

75° C or Higher

Line/Load Wiring Voltage Rating (120/240 VAC)

300 VAC Minimum

Line/Load Wiring Voltage Rating (480 VAC
systems)

600 VAC Minimum

Control Wiring

300 VAC Minimum


Allowable Wire Sizes:

Current
Rating of
System

Line
Connection

Load
Connections

Ground
Connections

Control
Circuit
Connections

20 Amp
40 Amp
70 Amp

14-8 AWG
12-4 AWG
10-1 AWG

14-2 AWG
14-2 AWG
14-2 AWG

14-4 AWG
14-4 AWG
14-4 AWG

22-10 AWG
22-10 AWG
22-10 AWG


NOTE:
Wire temperature and connector ampacity ratings are based on NEC 310-16 using
75°C copper wire derated for 50°C ambient environment.

Recommended Minimum Wire Sizes:

Current
Rating of
System

Line
Connection

Load
Connections

Ground
Connection

Control
Circuit
Connections

20 Amp
40 Amp
70 Amp

12 AWG
8 AWG
4 AWG

12 AWG
8 AWG
4 AWG

12 AWG
10 AWG
8 AWG

16 AWG
16 AWG
16 AWG


Electrical Inputs:

Heater open interlock switch

Contacts Rated for 120 VAC at 2.0 A

Cooling flow interlock switch

Contacts Rated for 120 VAC at 100mA

Heater Over-temp. thermo switch

Contacts Rated for 120 VAC at 100mA

Remote interlock switch

Contacts Rated for 120 VAC at 100mA


Table 3-1