Rola-Chem RC554XP ORP/pH Digital Controller User Manual

Page 14

Advertising
background image

Rola-Chem Digital Controller PN 554135 02/17/2014 Page: 14 of 20

C. Set-points not being reached/maintained


*

Factory setting for feed time is 0.6 sec on with 5 minute delay. Feeders may require longer feed

time. If time is too short, set-points will not be maintained. If time is too long, overfeeding
chemicals will occur. Correct time is dependent of multiple factors such as pool/spa water
volume, feeder output, chemical concentration and chemical needs.

* Controllers are designed to maintain set-points. Do not expect Controllers to make major

adjustments—major changes should be done manually.

* Pump/feeders must be large enough to reach desired set-points in a relatively short time.

Automation using controllers may require larger feeder or more concentrated chemicals than
system that uses continuous time controlled feeding (i.e. feeders only).



































Advertising