Dis con tin ued – Seametrics FT500B User Manual

Page 2

Advertising
background image

The FT500B is a batch controller designed for use with
SeaMetrics flow meters. Batch size is set using the
alphanumeric display, and relay outputs turn external fluid
controls off or on.

Installation

Mounting. Using three screws, mount the unit to any
secure surface. Drive the center screw first, before lifting
the unit into place. Leave the head extending slightly.
Slide the center mounting lug over this screw head, then
remove the terminal cover to find the other two holes.
Insert screws through these holes and tighten.

Sensor Connection. With the terminal cover removed,
locate the “Sensor” terminals. Following the Connections
diagram, connect flow sensor leads to the appropriate
terminals. Sensor cable can be threaded in through the
strain relief provided with the unit for sealing purposes.

Batch Control Connections. Follow the diagram to
connect to the relay outputs. Note that both Normally
Open and Normally Closed connections are provided.
It is not necessary to use terminals provided for prewarn
output unless a two-stage valving system is being used.

Power Connection. Following the Connections
diagram, connect power. If the unit is standard 115 VAC,
be sure to connect a ground wire for safety. The optional
12 VDC unit is supplied with a plug-in power converter.
Observe correct polarity when connecting this unit.

Programming

Program Mode. All programming is done in Program
Mode. The RUN/PROGRAM button turns this mode on
and off.

Units. Select the desired units with the

and keys.

The FT500B will read and batch in these units.

K-Factor. Select “Meter Change”. The display will read
“K-factor =...” Change this number to read the K-factor
which is correct for your sensor.

Update. It is not necessary to change the display update
time unless the display is excessively jumpy. Update
time can be increased to a maximum of 2,000
milliseconds (2 seconds).

Batch Size. Select Batch Change. The first setting is
the basic batch size. Use the

/ buttons to set this to

the desired size. The second setting is the prewarn
amount. This only needs to be set if a two-stage system
is being used. It represents the number of units before
the end of the batch at which the K1 relay will drop out.
In the typical application, the high-flow valve is connected
to K1, and the low-flow valve is connected to K2. When

the batch comes within the set number of units of the
end, the high-flow valve will close and the low-flow will
continue open until the end of the batch.

Display Contrast. Change this number only if the unit
is difficult to read, due to light conditions or position on
the wall.

Operation

Displays. When operating, either Batch, Rate, or Total
is always displayed.

Batch: This is the volume of flow since the
START button was pushed to start the batch.
Rate:

This is the rate of flow in the selected

units.
Total:

This is the running total accumulated

since the beginning of operation, or since the
last reset.

Batch Operation. Pushing the START button causes
the output relay(s) to energize. The relays remain
energized until the end of the batch unless the STOP
button is pushed. The RESUME button can be used to
return to operation after a mid-batch stop.

The Prewarn relay energizes at the same time as the
Batch relay, so that if dual valves are being used (high
flow and low flow) they will open at the same time.
However, at the set number of units before batch end
(“Prewarn” setting) the Prewarn relay will drop out. In
this way the flow can be lowered at the end of the batch
for greater precision.

Maintenance and Repair

Front Panel Removal. The front panel must be removed
to gain access to fuses, or to replace a printed circuit
board. Open the clear cover. Remove the two screws
on the left side and the two hex standoffs on the right.
Gently loosen the panel and lift it out. The display board
is attached, and will come with the panel. This exposes
the fuses which are on the power supply board.

Fuses. The power supply and the pulse output circuit
have fuse protection. The two fuses are on the power
supply board. Replace a blown fuse with a .5 amp.

Backup Battery. Programmed settings and total flow
are stored in battery-backed memory to protect them
from power failure. The life of the battery is approximately
ten years. It is recommended that the battery be changed
well before the end of its expected life. To change the
battery, first remove the front panel. The coin-shaped
battery is in a holder on the under side of the display
board. Remove and replace it with a BR2325 or
equivalent.

2 of 4

DIS

CON

TIN

UED

Advertising