2 troubleshooting – Spectrex 40/40R - Single IR Flame Detector User Manual

Page 49

Advertising
background image

TM 40/40R, Rev (4) November 2010

Troubleshooting

37

4.2 Troubleshooting

This section is intended to be a guide to correct problems which may happen

during normal operation.
Table 19: Troubleshooting Table

Problem

Cause

Corrective Action

LEDs Off
Fault Relay at N.O

0-20mA at 0mA

No power at the
unit

•

Check that the correct power
is sent to the detector.

•

Check power polarity.

•

Check wiring in the detector.

•

Send the detector back for
repairs.

Yellow LED flashes
at 4 Hz

Fault Relay at N.O

0-20mA at 0mA

Fault Detector

•

Low Voltage

•

Faulty Detector

•

Check the voltage at the
detector; verify at least 24V

at the detector terminal.

•

Send the detector back for

repairs.

Yellow LED flashes
at 4 Hz

Fault Relay at N.O
0-20mA at 2mA

BIT Fault

•

Faulty Detector

•

Clean detector window.

•

Re-power the detector.

•

Replace the detector.

Red LED

constantly on

If no fire exists,

then, detector
alarm latched

Perform Reset to the detector.

Alarm Relay at On
0-20mA at 20mA

Alarm condition

•

Check cause for alarm.

•

If no alarm, re-power the

detector.

•

Send the detector back for

repairs.

Advertising