Easicool™ precision air conditioning, Te ch nic al x-t yp e v, Technical data upflow units x type – Airedale EasiCool 6kW 64kW User Manual

Page 83: V6x - v10x, Electrical data

Advertising
background image

EasiCool™

Precision Air Conditioning

83

EasiCool Technical Manual 7525389 V1.1.0_02_2013

Te

ch

nic

al

X-T

yp

e

V

V6X - V10X

Technical Data Upflow Units X Type

Electrical Data

V6X-EZRE-0

V8X-EZRE-0

V10X-EZRE-0

Standard Condenser Match

1 x CR12

1 x CR16

1 x CR16

Max Mains Incoming Cable Size

mm²

6

6

6

Mains Supply

V

400V / 3PH + N / 50HZ

Control Circuit

VAC

24

24

24

Unit Data Full Function - X

(1)

Nominal Run Amps

A

20.0

21.0

21.2

Maximum Start Amps

A

42.4

51.4

58.6

Recommended Mains Fuse Size

A

25

25

25

Unit Data Cooling Only - X
Nominal Run Amps

(2)

A

9.2

10.2

10.4

Maximum Start Amps

A

31.6

40.6

47.8

Recommended Mains Fuse Size

A

16

16

16

Evaporator Fan - EC Motor Per Fan

Centrifugal Forward Curved DD EC - Designed to 25Pa ESP

Quantity

1

1

1

Maximum Electrical Input Power

(3)

kW

1.3

1.3

1.15

Full Load Amps

A

5.6

5.6

4.8

Locked Rotor Amps

A

5.6

5.6

4.8

Compressor - Per Compressor
Quantity x Motor Size

kW

1 x 2

1 x 2.6

1 x 3.3

Nominal Run Amps

A

3.6

4.6

5.6

Locked Rotor Amps

A

26

35

43

Type of Start

Direct On Line

Standard Condenser Match - AC Motor - Per Fan
Quantity

1

1

1

Maximum Electrical Input Power

kW

0.27

0.27

0.27

Full Load Amps

A

1.1

1.1

1.1

OPTIONAL EXTRAS
Electric Heating
Stage of Reheat

1

1

1

Number of Elements

3

3

3

Rating

kW

7.5

7.5

7.5

Current per Phase

A

10.83

10.83

10.83

Humidifier
Capacity

kg/hr

3

3

3

Rating

kW

2.25

2.25

2.25

Full Load Amps

A

3.25

3.25

3.25

Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Quantity
Maximum Electrical Input Power

(3)

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Standard Size Motor - EC Motor - Per Fan

Centrifugal Backward Curved DD EC - Designed to 25Pa ESP

Quantity

1

1

1

Quantity x Motor Size

(3)

kW

0.94

0.94

0.94

Full Load Amps

A

1.5

1.5

1.5

Condenser Fan Options
Standard Condenser Motor - EC Motor - Per Fan
Quantity

1

1

1

Maximum Electrical Input Power

(3)

kW

0.7

0.7

0.7

Full Load Amps

A

3.1

3.1

3.1

Mechanical

(1)

Entering air 24°C/45% RH ambient 35°C.

(2)

Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, these values may change with different ESP.

(3)

With Standard forward curved fan motors; Machine weight includes a refrigerant charge.

(4)

Backward curved EC fan options quote electrical power. All other options quote shaft power.

(5)

For refrigerant charges, refer to

Unit Refrigerant Charge (kg/Circuit)

.

(6)

Based on air temperature of 15.5°C leaving the evaporator coil.

(7)

Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to

Low Pressure Hot Water

.

Electrical

(1)

Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard

forward curved fan motors, for optional data, please contact Airedale.

(2)

Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional

data, please contact Airedale.

(3)

Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Advertising