Troubleshooting, It cooling logicool ™ onrak – Airedale OnRak 3kW 35kW User Manual

Page 55

Advertising
background image

IT Cooling

LogiCool

™ OnRak

IT Cooling

55

Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013

Troubleshooting

FAULT

POSSIBLE CAUSE

REMEDY/ACTION

Unit will not start

No power

Check power supply to the controller.


Wired incorrectly

Check wire connections in accordance with wiring
diagram on control panel.

Loose wires

Check all wires, connections, terminals etc.

Fan not operating - power
on

Power supply failure

Check power supply at circuit breaker.


Wiring to motor

Check voltage at motor terminals.


Motor / fan assembly jammed

Isolate unit and check free rotation of motor/fan
assembly, if faulty

– replace.

Power disconnected to fans.

Carefully check status of power disconnect socket.

Status indication LED faulty Wired incorrectly

Check that the wiring to the LED has the correct
polarity.

Check that the terminations are correct.

Display faulty

Does not illuminate

Faulty cable- Replace cable.

Faulty display

– Replace display.

Wrong display address

Change address of display (see controls section)

No Cooling

Low water flow through coil

Ensure any chilled water valves are open and not
in bypass.

Ensure that any solenoid valves are open when
there is a demand for cooling.

Water temperature sensor faulty. The sensor has
failed causing the valves on the unit to close.

UPS

The UPS system does not operate
correctly

Please refer to the UPS documentation / fault
codes. Various solutions are available from
changing battery modules to module restart.

Water Leak Detection

Damaged flexible hose

Ensure that the flexible hose is not rubbing on the
coil or sheet metal in the vicinity of the door.

Condensation has formed on coil

Check operating conditions ensuring that the unit
operates with its dew point control feature.