Heat pump heating modulating capacities, Blucube ™ condensing unit, Condensing units – Airedale BluCube 10-48kW User Manual

Page 52

Advertising
background image





BluCube

Condensing Unit

52

Condensing Units

Technical Manual : 7206188 V1.6.0_07 2014

Heat Pump Heating Modulating Capacities

Winter Ambient (°C)

-5

0

5

10

15

Unit

Cond

Temp

(°C)

Output

(kW)

Input

(kW)

Output

(kW)

Input

(kW)

Output

(kW)

Input

(kW)

Output

(kW)

Input

(kW)

Output

(kW)

Input

(kW)

CUR092V16-VHP-0

40

12.1

4.4

13.6

4.4

15.2

4.5

17.0

4.5

18.9

4.6

45

12.1

4.8

13.6

4.9

15.1

5.0

16.8

5.0

18.6

5.1

50

N/A

N/A

13.5

5.4

15.0

5.5

16.6

5.5

18.3

5.6

55

N/A

N/A

N/A

N/A

14.8

6.0

16.4

6.1

18.0

6.2

CUR092V20-VHP-0

40

15.9

5.7

17.7

5.8

19.6

5.9

21.7

5.9

23.9

6.0

45

15.9

6.2

17.7

6.4

19.5

6.5

21.5

6.5

23.7

6.6

50

N/A

N/A

17.6

7.0

19.4

7.1

21.4

7.2

23.4

7.3

55

N/A

N/A

N/A

N/A

N/A

N/A

21.2

8.0

23.2

8.1

CUR092V25-VHP-0

40

19.0

7.0

21.0

7.0

23.2

7.0

25.5

7.0

28.0

7.0

45

19.1

7.9

21.1

7.8

23.2

7.8

25.4

7.7

27.8

7.7

50

N/A

N/A

21.1

8.8

23.2

8.7

25.3

8.6

27.7

8.6

55

N/A

N/A

N/A

N/A

N/A

N/A

25.3

9.7

27.5

9.6

CUR092V29-VHP-0

40

21.6

8.2

23.9

8.2

26.4

8.1

29.0

8.1

31.7

8.1

45

21.7

9.2

24.0

9.2

26.4

9.1

28.9

9.1

31.6

9.1

50

N/A

N/A

N/A

N/A

26.5

10.2

28.9

10.2

31.4

10.1

55

N/A

N/A

N/A

N/A

N/A

N/A

28.9

11.5

31.3

11.4

CUR122V35-VHP-0

40

27.9

12.3

31.0

12.4

34.5

12.4

37.9

12.5

41.8

12.6

45

28.1

13.4

31.1

13.5

34.5

13.5

37.8

13.6

41.6

13.7

50

N/A

N/A

N/A

N/A

34.4

14.8

37.7

14.8

41.3

14.9

55

N/A

N/A

N/A

N/A

N/A

N/A

37.5

16.2

40.9

16.3

CUR122V40-VHP-0

40

32.7

14.1

36.0

14.2

39.8

14.3

43.4

14.3

47.6

14.4

45

33.0

15.4

36.3

15.4

39.9

15.5

43.5

15.6

47.4

15.7

50

N/A

N/A

N/A

N/A

40.0

16.9

43.5

17.0

47.3

17.0

55

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

47.0

18.6

Notes:
1

Output kW refers to the compressor duty.
All performance data is supplied in accordance with BS EN 14511-1:2013

2

Input kW refers to the compressor and fan input power only.

Advertising