CONDENSERS

Condenser

17

Technical Manual :6666879 1.1.0 02_2013

/2012

Sound Data

METHOD OF SOUND
MEASUREMENT

All sound data quoted has been measured in the third-octave band limited values, using
a Real Time Analyser calibrated sound intensity meter in accordance with
BS EN ISO9614 Part 1: 1995.

All Sound Power Levels quoted are calculated from measured sound intensity according
BS EN ISO9614 Part 1: 1995.

SEMI HEMISPHERICAL

Sound Pressure Levels are calculated from sound power using the semi-hemispherical
method where the noise source is in junction with 2 boundaries i.e. the floor and 1 wall.







SOUND DATA - STANDARD FAN

IMPORTANT

The sound data quoted is based on the unit having the STANDARD FAN running at
FULL SPEED under normal operating conditions.

For sound data of optional fan selections, please contact Airedale.

Horizontal

Sound

Overall

dB(A)

Frequency (Hz) dB

Measurement

63

125

250

500

1000

2000

4000

8000

CR12

Power

74

72

83

76

68

68

65

60

50

Pressure

@10m

46

44

55

48

40

40

37

32

22

CR16

Power

74

72

83

76

68

68

65

60

50

Pressure

@10m

46

44

55

48

40

40

37

32

22

CR22

Power

78

82

87

74

74

73

70

63

62

Pressure

@10m

50

54

59

46

46

45

42

35

34

CR26

Power

82

83

80

82

79

78

74

67

59

Pressure

@10m

54

55

52

54

51

50

46

39

31

CR30

Power

78

82

87

74

74

73

70

63

62

Pressure

@10m

50

54

59

46

46

45

42

35

34

CR35

Power

82

83

80

82

79

78

74

67

59

Pressure

@10m

54

55

52

54

51

50

46

39

31

CR50

Power

81

85

90

77

77

76

73

66

65

Pressure

@10m

53

57

62

49

49

48

45

38

37

CR60

Power

85

86

83

85

82

81

77

70

62

Pressure

@10m

57

58

55

57

54

53

49

42

34

CR65

Power

81

85

90

77

77

76

73

66

65

Pressure

@10m

53

57

62

49

49

48

45

38

37

CR75

Power

85

86

83

85

82

81

77

70

62

Pressure

@10m

57

58

55

57

54

53

49

42

34

CR80

Power

83

80

90

80

77

79

75

68

67

Pressure

@10m

55

52

62

52

49

51

47

40

39

CR95

Power

87

88

85

87

84

83

79

72

64

Pressure

@10m

59

60

57

59

56

55

51

44

36

CR105

Power

82

80

90

80

77

79

75

68

67

Pressure

@10m

55

52

62

52

49

51

47

40

39

CR130

Power

87

88

85

87

84

83

79

72

64

Pressure

@10m

59

60

57

59

56

55

51

44

36

CR140

Power

84

81

90

81

78

81

77

70

69

Pressure

@10m

56

53

62

53

50

53

49

42

41

CR165

Power

88

89

86

88

85

84

80

73

65

Pressure

@10m

60

61

58

60

57

56

52

45

37