F-2000 – Blue-White F-2000 – Solvent Weld PVC Tee Fitting User Manual
Page 11
Advertising

F-2000
Page 11
Example 3:
A solenoid valve must open if the flow rate goes above 225 gallons per minute.
Step 1
Set the SETPOINT MODE SELECTION SCREEN] to SETPOINT - RATE.
Step 2
Set SETPOINT - RATE - 1, screen for a high trigger value of 225.
Step 3
Set SETPOINT - RATE - 2, screen for a high release value of less than 225. Example: 220
Step 4
Set SETPOINT - RATE - 3, screen for a low trigger value of 0. (Low alarm not used).
Step 5
Set SETPOINT - RATE - 4, screen for a low release value of 0. (Low alarm not used).
Step 6
Set SETPOINT - RATE - 5, to the desired alarm delay silencer time from 0 - 999 seconds (optional).
Step 7
Wire the value to the normally open terminals of the relay terminal block. See page 16.
Release
220
GPM
Trigger
225
GPM
Open Valve
Flow