Specifications, Ordering information – Adam Equipment Adam-4000 User Manual

Page 23

Advertising
background image

www.advantech.com/products

Online Download

4-

8

5

44

10

CompactPCI

9

Plug-in I/O

8

AWS

7

FPM

6

IPPC

TPC

RS-485 I/O

3

UNO

2

BAS

1

PAC & Software

11

Signal Conditioning

12

USB I/O

13

Motion Control I/O

14

Ethernet Switch

15

EDG

16

ICOM

17

Ethernet I/O

2-ch Counter/Frequency

Modules (with

7-segment LED Display)
4-ch Voltage Input Surge

Protection Module

ADAM-4080/4080D

ADAM-4914V

Specifications

General

Connectors

2 x Plug-in terminal block (#14 ~ 22 AWG)

Power Consumption

2.0 W @ 24 V

DC

Power Input

Unregulated 10 ~ 30 V

DC

Humidity

5 ~ 95% RH

Operating Temperature -10 ~ 70° C (14 ~ 158° F )
Storage Temperature

-25 ~ 85° C (-13 ~ 185° F)

Watchdog Timer

System (1.6 second)

Support Protocol

ASCII command

LED Indicators

5-digit readout, CH 0 or CH 1 (programmable)
(ADAM-4080D only)

Counter Input

Channels

2 independent 32-bit counters

Input Frequency

50 kHz max.

(non-isolation)

Input Pulse Width

>10 μs.

Input Mode

lsolated or non-isolated

Isolated Input Level

Logic level 0: +1 V max.

Logic level 1: 3.5~30 V

Isolation Voltage

2500 V

RMS

Non-isolated

Programmable threshold:

Input Level

Logic level 0: +0.8 V max.

Logic level 1: 2.4 ~ 5.0 V

Maximum Count

4,294,967,295 (32 bits)

Preset Type

Absolute or relative (ADAM-4080 only)

Programmable Digital

2 μs ~ 65 ms

Noise Filter
Alarm

ADAM-4080: Alarm comparators on each counter
ADAM-4080D: High and Low comparators on counter 0

Frequency Measurement

Range

5 Hz ~ 50 kHz

Programmable Built-in 1 or 0.1 second
Gate Time

Digital Output

Channels

2

Open Collector

30 V, 30 mA max. load

Power Dissipation

300 mW for each channel















ADAM-4080/4080D

Ordering Information

ADAM-4080/4080D

2-ch Counter/Frequency Modules

(with 7-segment LED Display)

ADAM-4914V

4-ch Voltage Input Surge Protection Module

ADAM-4914V

Specifications

General

Connectors

2 x Plug-in terminal block (#14 ~ 22 AWG)

Humidity

5 ~ 95% RH

Operating Temperature -10 ~ 70

° C

(14 ~ 158

° F

)

Storage Temperature -25 ~ 85

° C

(-13 ~ 185

° F

)

Input Channels

4 differential voltage and thermocouple input

Performance

Discharge Current

5000 A (8/20 μsec.)

Discharge Voltage

Between Lines: 18 V min.
Line to GND: 350 V max.

Internal Series

Approx. 20

Ω including

Resistance

return

Max. Surge Voltage

Between Lines: 23 V min.
Line to GND: +4,000 V max.

Leakage Current

Between Lines:

≤ 10 μA @ 7.5 V

DC

Line to GND:

≤ 5 μA @ +140 V

DC

Maximum Line Voltage 10 V
Response Time

≤ 0.1 μsec.







Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com