5.0 SPECIFICATIONS

RH Performance Data
Sensing Element

Capacitive Polymer

Humidity Operating Range

0 to 99% RH (non-condensing)

Accuracy at 68°F (20°C)

2%, 3%, 5%

Hysteresis

<1.5%

Repeatability

<0.5%

Long Term Stability

<1%/year @ 68°F (20°C), 50% RH

Electrical Data

Signal Outputs
Current (2-wire ckt.)

4 to 20 mA

Field Selectable Voltage (3-wire ckt.)

0 to 5 VDC, 0 to 10 VDC

Excitation
0 to 10 VDC

13.5 to 30 VDC

0 to 5 VDC, 4 to 20 mA

12 to 30 VDC

Maximum Load (Current only)

Ω = (Supply - 10) / 0.02

Electrical Termination

Pluggable Terminal Block (5mm Pitch)

Wiring Protection

Reverse Excitation

CE Compliance

EMC Directive 2004/108/EC

Temperature Sensing Options (Passive)

T1 Thermistor Output

NTC 10K

Ω @ 77°F/25°C (Direct Connect)

Type II

T2 RTD Output

1000

Ω @ 32°F/0°C (Direct Connect)

385 Platinum Curve

Temperature Sensing Options (Active)

Signal Ouput Options (includes humidity output):
Current

4 to 20 mA

Field Selectable Voltage

0 to 5 VDC, 0 to 10 VDC

Available Ranges:

Accuracy:

T3 (-50°C to 60°C)

±0.6°C (20°C @ 50%)

T5 (-10°C to 60°C)

±0.4°C (20°C @ 50%)

Environmental Data

Operating Temperature °F (°C)

-40 to 140 (-40 to 60)

Storage Temperature °F (°C)

-40 to 158 (-40 to 70)

Moisture Resistance

IP65, NEMA-4 (Duct & Outside Air)

Solar

UV Resistance (Outside Air)

Flammability Rating

94-V0

Compliance

RoHS and CE Compliant

Physical Description

Enclosure
Wall Mount

ABS 94-V0

Duct & Outside Air

Poly Carbonate 94-V0

Probe (Duct & Outside Air)

Aluminum

Weather Shield (Outside Air)

Porous Polyethylene