UEi Test Instruments PSMR1 User Manual

Psmr1, Phase sequence & motor rotation

Advertising
background image

1-800-547-5740 • Fax: (503) 643-6322

www.ueitest.com • email: [email protected]

PSMR1

Phase

Sequence & Motor

Rotation

INSTRUCTIONAL MANUAL

Introduction

All the information you need in one device. Verify
correct wiring to avoid damage.

Use the PSMR1 to check supply line phase
orientation for devices such as scroll
compressors or motors. Works on 45-70 Hz
and on voltages between 100 and 600 VAC.
Five indicators give you information about
open phases, and indicate the sequence of the
three lines. Use the motor rotation tester side
of the meter to verify the rotation direction of
the motor shaft.

Note: Follow all warnings to ensure
safe operations.

Safety Notes

• Read the following safety information

carefully before attempting to operate or
service the meter.

• Use the meter only as specified in this

manual; otherwise the protection provided
by the meter may be impaired.

• Rated environmental conditions:

1. Indoor use.
2. Installation Category III.
3. Pollution Degree 2.

4. Altitude up to 6560 feet (2000 meters).
5. Relative humidity 80% Max.
6. Ambient temperature 32 - 104˚F (0 - 40˚C).

• Observe the international electrical symbols

listed below:

Meter is protected throughout by double
insulation or reinforced insulation.

WARNING! Risk of electric shock.

CAUTION! Refer to this manual before
using the meter.

Alternating current.

Features

• Three functions in one unit including open phase,
phase sequence and motor rotation indication.

• This model is ideal for installing conveyor lines,
pump systems and interconnected drivers.

• Identifies 3-phase sequence and open phase check.

• Battery operated.

• Meets EN61010-1 safety requirements.

• Complete with three large alligator clips.

Descriptions

1. Phase rotation input terminal

2. Open phase indicator

3. Phase rotation indicator

4. Motor tester power switch

5. Motor tester power indicator

6. Motor rotation indicator

7. Motor rotation input terminal

Measuring Methods

Operations 3 phase rotation tester:

1. Connect the test lead to 3-phase input

terminals by R-S-T.

2. Connect color alligator clips to the

terminals of a 3-phase power source.
Connecting order may be optional.

3. Make sure that all of the three lamps for

open phase check are on. If so, there is no
open phase. When any of the three lamps
is not on, there is open phase.

Continued on other side

UE

PSMR1

Phase & Motor Rotation Tester

Limited Warranty

The PSMR1 is warranted to be free from defects in
materials and workmanship for a period of three year’s
from the date of purchase. If within the warranty period
your instrument should become inoperative from such
defects, the unit will be repaired or replaced at UEi’s
option. This warranty covers normal use and does not
cover damage which occurs in shipment or failure which
results from alteration, tampering, accident, misuse,
abuse, neglect or improper maintenance. Batteries and
consequential damage resulting from failed batteries are
not covered by warranty.

Any implied warranties, including but not limited to
implied warranties of merchantability and fitness for
a particular purpose, are limited to the express
warranty. UEi shall not be liable for loss of use of
the instrument or other incidental or consequential
damages, expenses, or economic loss, or for any claim
or claims for such damage, expenses or economic loss.
A purchase receipt or other proof of original purchase
date will be required before warranty repairs will be
rendered. Instruments out of warranty will be repaired
(when repairable) for a service charge. Return the unit
postage paid and insured to:

1-800-547-5740 • FAX: (503) 643-6322

Service: (800) 308-7709

www.ueitest.com • Email: [email protected]

This warranty gives you specific legal rights. You may also
have other rights which vary from state to state.

®

1

2

3

4

6

5

7

Copyright © 2003 UEi

PSMR1-MAN 7/03